Trial Operation And Testing; Test Items - Daikin RX15RMVJU Installation Instructions Manual

Hide thumbs Also See for RX15RMVJU:
Table of Contents

Advertisement

[For wireless remote controller]
1) Press
and select the COOL operation.
2) Press
twice. "Test" is displayed.
3) Press
within 10 seconds, and the forced cooling operation starts.
• Forced cooling operation will stop automatically after about 15 minutes.
To stop the operation, press
[For FTXR models]
„Using the indoor unit ON/OFF switch
Press the indoor unit ON/OFF switch for at least 5 seconds. (The operation will start.)
• Forced cooling operation will stop automatically after about 15 minutes.
To stop the operation, press the indoor unit ON/OFF switch.
„Using the indoor unit's remote controller
1) Press
and select the COOL operation.
2) Press
to turn on the system.
3) Press
,
and
4) Press
, select "
", and press
• Forced cooling operation will stop automatically after about 30 minutes. To stop the operation, press

Trial Operation and Testing

1.
Trial operation and testing
Refer to the installation manual for the indoor unit.
2.

Test items

Indoor and outdoor units are installed properly on solid bases.
No refrigerant gas leaks.
Refrigerant gas and liquid pipes and indoor drain hose extension are
thermally insulated.
Draining line is properly installed.
System is properly grounded.
The specifi ed wires are used for inter-unit wiring.
Indoor or outdoor unit's air inlet or air outlet are unobstructed.
Stop valves are opened.
Check that the connector of the lead wires of the decoration panel is
connected securely.
Indoor unit properly receives wireless remote control commands.
English
.
at the same time.
for confi rmation.
Test items
Symptom
Fall, vibration, noise
Incomplete cooling/heating function
Water leakage
Water leakage
Electrical leakage
No operation or burn damage
Incomplete cooling/heating function
Incomplete cooling/heating function
Louvers do not move
No operation
.
Check