Figure 22: JEHR-0180/0210-B2-L-3
B1
1
3
5
14
13
I >
I >
I >
2
4
6
L1
L2
L3
N
380-415V 3N~ 50Hz
MODEL
JEHR/JEHCCU0180B(C)L3
JEHR/JEHCCU0210B(C)L3
Figure 23: JEHS-0200/0250/0300/0350-B2-M-1
B1
1
3
5
I >
I >
I >
2
4
6
PE
L
N
220-240V 1~ 50Hz
MODEL
JEHS/JEHSCU0200B2(C)M1
JEHS/JEHSCU0250B2(C)M1
JEHS/JEHSCU0300B2(C)M1
JEHS/JEHSCU0350B2(C)M1
Issue: 01.06.2023
F1U
3.15A
K1M
1
3
5
K1M
2
2
4
6
PE
M
GRN/YLW
3~
M1C
NOTE 1:ONLY FOR NON PUMP DOWN SYSTEM, REMOVE LINK WIRE FROM TERMINALS 3 & 4 TO CONNECT
EXTERNAL THERMOSTAT FOR CONTROLLING THE COMPRESSOR ACTIVATION.
INDICATOR:
-- : FIELD WIRING
A1P: FAN SPEED CONTROLLER
B1 SETTING,(A)
B1: MOTOR CIRCUIT BREAKER
4.0
C1: FAN CAPACITOR
E1HC: CRANKCASE HEATER
5.5
F1U: FUSE
F1U
3.15A
K1M
1
3
K1M
2
4
2
C1
R
S
C
M
GRN/YLW
1~
M1C
NOTE 1:ONLY FOR NON PUMP DOWN SYSTEM, REMOVE LINK WIRE FROM TERMINALS 3 & 4 TO CONNECT
EXTERNAL THERMOSTAT FOR CONTROLLING THE COMPRESSOR ACTIVATION.
B1 SETTING,(A)
INDICATOR:
13.0
-- : FIELD WIRING
A1P: FAN SPEED CONTROLLER
13.0
B1: MOTOR CIRCUIT BREAKER
C1: RUN CAPACITOR
17.0
C2: FAN CAPACITOR
21.0
E1HC: CRANKCASE HEATER
BRN
BLU
14
13
ALM
A1P
GRN/YLW
1
1
2
C1
M
GRN/YLW
1~
N3
M1F
BRN
BLU
14
13
ALM
A1P
GRN/YLW
1
1
2
C2
M
GRN/YLW
1~
N3
M1F
5
K1M
GRY
S1PH
3
4
HP
P<
1
GRN/YLW
LP
P>
S1PL
4
NOTE 1
3
A1
K1M
A2
BLU
BLU
N2
N1
K1M: CONTACTOR
M1C: COMPRESSOR
M1F: CONDENSER FAN
S1PH: HIGH PRESSURE SWITCH
S1PL: LOW PRESSURE SWITCH
5
K1M
GRY
S1PH
3
4
HP
P<
1
GRN/YLW
LP
P>
S1PL
4
NOTE 1
3
A1
K1M
A2
BLU
BLU
N2
F1U: FUSE
K1M: CONTACTOR
M1C: COMPRESSOR
M1F: CONDENSER FAN
S1PH: HIGH PRESSURE SWITCH
S1PL: LOW PRESSURE SWITCH
21
22
E1HC
21
22
E1HC
GRN/YLW
N1