Recommended Cables
Recommended cables for this panel are as follows:
Manufacturer
Product Name
AEI
AEI
Firetec
Draka
FiretufPlus
Draka
Firetuf
Pirelli
FP Plus
Pirelli
FP200 Gold
ASCABLE
2 x 1,5 LHR
ASCABLE
2 x 2,5 LHR
(1) For a definition of 'Standard' and 'Enhanced' cable requirements and their different applications, refer to
BS 5839-1, Section 26. Enhanced cable is typically required for spur sounder outputs while standard cables
may be adequate for other fire-related I/O, provided there is diverse cable routing.
22 June 2011
Part Number
MICC
2L1.5
298-052
FTPLUS2E1.5RD
FTZ 2E1.5
FP Plus 2x1.5 Red
FP200 Gold 2x1.5 Red
2 x 1,5 LHR
2 x 2,5 LHR
Main
EMC Considerations
Following the above instructions and by using suitable screened cables EMC
problems will be avoided.
In particularly difficult EMC environments, or where non-preferred cabling is
used, it is possible to fit ferrite sleeves to cables entering the panel, in particular
the power supply input, sounder and auxiliary output cables.
The ferrite sleeves (A) should be fitted over all the conductor(s) and as close as
possible to the entry point of the cable. If required, use a cable tie (B) - not
supplied - to hold the ferrite in position.
If additional ferrites are required these can be purchased from your
supplier.
Extinguishing control panel. User manual
(1)
Type
Enhanced
Standard
Enhanced
Standard
Enhanced
Standard
Fire resistant and halogen free
Fire resistant and halogen free
Zones
8