FLOWTECH flowcon Operation And Maintenance Manual

Vsd - f inverter

Advertisement

Quick Links

1
flow
con
©
VSD - F Inverter
OPERATION AND
MAINTENANCE MANUAL
First Publication Date: 01/09/2020
Revision:
Revision Date:

Advertisement

Table of Contents
loading

Summary of Contents for FLOWTECH flowcon

  • Page 1 flow © VSD - F Inverter OPERATION AND MAINTENANCE MANUAL First Publication Date: 01/09/2020 Revision: Revision Date:...
  • Page 2: Table Of Contents

    OPERATION & MAINTENANCE CONTENTS General Information Safety Information Safety Warnings & Precautions Customer / Contractor Responsibilities Authorised operators Warranty Technical assistance Technical description Intended use Improper use Technical features Operating conditions Product overview Pushbuttons functions Interface System icons Display area Operating icons Safety Transport and handling...
  • Page 3: General Information

    General Information These instructions are to assist in the installation of the flowcon VSD - F Inverter please follow them carefully. If, having read this Operation & Maintenance Manual, there is any doubt about any aspect of the installation please don't hesitate to contact our technical team.
  • Page 4: Safety Information

    Water Solutions. This document is intended for ALL installers, operators, users and persons carrying out maintenance of this equipment and must be kept with the equipment, for the life of the equipment and made available to all persons at all times.
  • Page 5: Safety Warnings & Precautions

    Wait more than 5 minutes after turning off the power supply before performing maintenance or inspection. Hazard of electric shock. Disconnect incoming power before working on this unit. WARNING! - The inverter should be protected separately against ground fault. HAND-PAP Observe the regional regulations for electrical installation! flowcon VSD - F Inverter...
  • Page 6: Customer / Contractor Responsibilities

    exclamat CAUTION! - It is strongly recommended that all electrical equipment conforms to National Electrical Codes and local regulations. Only qualified personnel should perform installation, alignment and maintenance. The manufacturer reserves the right to alter the technical data in order to make improvements or update information. exclamat CAUTION! - Failure to observe these rules will render the guarantee invalid.
  • Page 7: Authorised Operators

    Flowtech Water Solutions Ltd. Technical description Flowcon VSD - F Inverter is a frequency converter that could be mounted in a control box or on a motor. The frequency converter is manufactured in accordance to EN61800-3:2005-07 acc. EN55011 limit B until a 7,5 kW, limit A1 until a 55kW.
  • Page 8: Technical Features

    Technical features Supply voltage: 3~380 VAC-10% ÷ 3~480 VAC+5% IP protection: IP55 Liquid Crystal Display Keyboards: 6 pushbuttons Digital input: - 2 Float switches - MAX/min curve enable - 2nd set-point enable - Remote On/off control Analog input: - Primary transducer - Secondary transducer Digital output: Up to 3 alarm output or Start/stop signal...
  • Page 9: Product Overview

    Product overview Flowcon VSD - F inverter is a frequency converter for pumps,that implement the following operating modes: Constant pressure; Proportional pressure; Constant temperature; Constant flow; Night mode; Fixed speed; Constant pressure mode and Proportional pressure mode are available also in cascade mode.
  • Page 10: Interface

    Interface The graphic interface of the display is divided in three visualization areas: System icons Display area Operating icons System icons AUTO MODE The system is operating in auto mode. MANUAL MODE The system is operating in manual mode. SET-UP MODE ACTIVATED It shows that the set-up menu is activated.
  • Page 11: Display Area

    (maximum frequency) for 50 Hz motors, and between 30 and 60 Hz for 60 Hz motors. The running up time from 0 to 30 Hz and the running down time from 30Hz to 0, must be as short as possible, according to the motor power to operate. flowcon VSD - F Inverter...
  • Page 12: Safety

    Safety Before using the product it is necessary to acknowledge all the information about safety. All the technical information, operating procedures, and the indications described in this manual, from transport and handling to final dismantling. The specialized technicians must observe the rules, standards and laws of the country where the frequency converter is sold.
  • Page 13: Transport And Handling

    TABLE 1. In this case wiring tips should be used. Wrong connections could tamper the electronic circuit of the frequency converter. Before any kind of electrical operation on the frequency converter, just installed wait 10 minutes. flowcon VSD - F Inverter...
  • Page 14: Power Supply Connection

    Power supply connection Electrical supply must comply with the description. If the electric control box is connected to an electric plant with a differential switch (ELCB) or a Ground Fault Circuit Interrupter (GFCI) as a further protection, these devices must comply the following characteristics: Suitable to control leakage current and, in case of short pulsed leakage current.
  • Page 15: Float Switch Connection

    Connect the transducer (either pressure, temperature or flow rate) to the delivery manifold of the pressure boosting set. It is advised to install the pressure transducers on the same point of the delivery manifold and complete the installation with a pressure gauge. flowcon VSD - F Inverter...
  • Page 16: Programming Guide

    Cascade mode electrical connection Connect the supply cables to the motors and to the power supply following the instructions. The connection with the power supply must be made with installation of a tripolar circuit breaker (one for each frequency converter) with proper size and with a B-type differential switch. Cascade mode expansion board installation The cascade mode expansion board must be installed perpendicularly to the control board, checking that the connectors are properly connected, and that the board fits into the slides.
  • Page 17: Programming Parameters

    AE – Advanced parameter: this allows for the display of secondary parameters which can be useful for system diagnostics. AE01 Software release AE02 Last 10 alarms AE03 Supply voltage (V) AE04 Frequency converter output voltage(V) AE05 Total working hours AE06 Number of starts Supply voltage visualization example flowcon VSD - F Inverter...
  • Page 18: Operating Mode Programming

    By pushing the menu button the UP parameter appears. Select the AE parameter by pushing the plus up to arrive at the correct parameter AE, confirm with enter. Select the parameter AE02 by pushing the plus button and confirm with enter. Supply voltage is displayed. Programming To enter programming, select menu.
  • Page 19 On demand [bar] To ensure the system works properly, the primary transducer (B1-B4 clamps) must be always connected to the delivery pipe, and the secondary transducer (B5-B8 clamps) must be always connected to the suction pipe. flowcon VSD - F Inverter...
  • Page 20 Minimum run frequency and pre-pause frequency settings The frequency converter is equipped with an automatic stop system in case of low water. In the case where the system does not guarantee the correct stop of the pump, it is possible to set manually the following values: Frequency before stop Minimum run frequency...
  • Page 21 (parameter SA03) it’s necessary change the value of the parameter AP16 from “Off” to “FM”. The system will restart when the difference between the set-point pressure and system pressure becomes lower than the value of parameter PP08. flowcon VSD - F Inverter...
  • Page 22 Constant temperature operating mode. Constant temperature operating mode keeps constant the temperature at a point in the system. In this operating mode the frequency converter keeps constant the temperature. For this operating mode must be defined the type of system where the frequency converter will operate: Heating systems (Heat): in these systems an increase of the pump frequency will correspond to an increase of the temperature of the transducer.
  • Page 23 Primary transducer minimum value AP05 Primary transducer maximum Value Man3 Remote control activation Man4 Minimum value for remote control On demand [Hz] The maximum frequency (parameter UP03) will be related to the maximum value of the external reference. flowcon VSD - F Inverter...
  • Page 24 This option use a feedback of a temperature transducer connected. (secondary transducer electrical connection). Because on Flowcon VSD - F inverter only two analog inputs are available, this option does not allow other options or operating modes which need 2 transducers (i.e. differential mode).
  • Page 25 Condition Operation Stand-by Alarm Er01 Alarm Er02 Alarm Er03 Alarm Er04 Alarm Er05 Alarm Er06 Alarm Er07 Alarm Er08 Alarm Er09 Alarm Er10 Alarm Er11 Alarm Er12 Alarm Er13 Alarm Er14 Alarm Er15 Alarm Er16 flowcon VSD - F Inverter...
  • Page 26 Alarm Er17 Alarm Er18 Alarm Er19 All alarms The parameter AP35 allows to select the activation condition for the relay connected to terminals A6- A10. The values and conditions for relay activation are here below reported. Value AP35 Condition Alarm Er01 Alarm Er02 Alarm Er03 Alarm Er04...
  • Page 27 After the electrical connection (see section 7.4), set parameter AP11 on the frequency converter on the value “UF” and the parameter AP54 with the number of pumps of the booster set (Both fixed speed pumps and variable speed pumps). flowcon VSD - F Inverter...
  • Page 28: Starting Pump

    Enabling twin-pump operation This operating mode works only with 2 pumps and works with the followings operating modes: - Constant pressure mode - Proportional pressure mode - Constant temperature mode - Constant flow rate mode In this operating mode only one pump works and the other one is for total reserve. To enable twin-pump mode the parameter AP11 must be set to “dP”, define which frequency converter works as master “MAS”...
  • Page 29: Vessel Pressure

    The device must be dismantled in different way from normal. For disposal must be followed the actual laws and regulation of the country where the disposal is made, other than the international laws and norms for ambient protection. flowcon VSD - F Inverter...
  • Page 30 Parameter table list...
  • Page 31: Parameters Up - User Parameters

    2 = m3/h 3 = Hz 4 = °C AP08 Secondary transducer minimum value AP09 Secondary transducer maximum value AP10 Secondary transducer DiFF = Differential mode mode nMOd = Night mode REM = Remote control flowcon VSD - F Inverter...
  • Page 32 AP11 Cascade mode UU = Cascade 2-6 converters UF = Single converter cascade dP = Twin pump AP12 Master/Slave setting MAS = master SLA = slave AP13 Pump address SLA1÷SLA5 SLA1 AP14 Rump-up AP15 Rump down AP16 Stand-by mode FM = minimum frequency setting PrP = pre-pause frequency...
  • Page 33 AP50 Reset to factory set- nO, yES AP51 Safe-start activation On, Off AP52 Safe-start operating (Hz) frequency AP53 Safe-start time (min) AP54 Number of pump of the booster set AP55 Delta/Star start delay time flowcon VSD - F Inverter...
  • Page 34: Parameter Sa - Service Assistance Settings

    Parameter SA – service assistance settings N° Description Values Standard Modification SA01 Nominal motor voltage SA02 Carrier frequency (Hz) 7010 SA03 Minimum operating (Hz) frequency SA04 Phase missing percentage SA05 Restore attempt number SA06 Attempt time SA07 I2t Threshold limit SA08 Motor heating delay time Parameter PC –...
  • Page 35: Parameter Pp - Proportional Pressure Settings

    (proportional gain) PP11 Pressure PID (integral time constant) PP12 Pressure PID 1000 (derivative time constant) PP13 Cascade mode start (bar) fall pressure set-up PP14 Cascade mode restart delay PP15 Cascade mode fall (bar) pressure limit set-up flowcon VSD - F Inverter...
  • Page 36: Parameter Tc - Constant Temperature Setting

    Parameter tC – Constant temperature setting N° Description Values Standard Modification tC01 System type HEAt HEAt COOL COOL tC02 Restart temperature (°C) tC03 System dynamic tC04 Temperature PID 3000 (proportional gain) tC05 Temperature PID (integral time constant) tC06 Temperature PID 1000 (derivative time constant)
  • Page 37: Alarms

    Er16 Internal Hardware error Contact technical assistance. Er17 Not implemented Er18 Cascade mode communication error Check the RS485 connection. Er19 Cascade expansion card failure Cascade expansion card not connected or faulty. flowcon VSD - F Inverter...
  • Page 38: Troubleshooting Chart

    Troubleshooting chart Fault Probable cause Possible solution Short-circuit Motor or cable short-circuit Check motor connections Wrong power supply connection Check power supply voltage Wrong connection of the cable shield Frequency converter Ambient temperature too high Check the condition of overheating One or more frequency converter installation (see section 3.1) fans faulty...
  • Page 39 Unit 1 Lock Flight Buildings, Wheatlea Industrial Estate, Wigan, Greater Manchester WN3 6XP United Kingdom 9001 : 2015 REGISTERED Membership No. 700106 Certificate No. 185352020 Copyright © 2020 • All Rights Reserved • Flowtech Water Solutions Limited • Company Number: 05125479 • VAT Number: 836 8024 19...