Start-Up Procedure - Riello RS 310/E BLU Installation, Use And Maintenance Instructions

Forced draught gas burners
Table of Contents

Advertisement

6.8

Start-up procedure

Check that the operator panel display shows the heat request
and "OFF Upr": this means it is necessary to set the modulation
curve of the burner.
P
Access the Parameters Level referring to "Access procedure with
password" on page 37.
The display screen displays the parameters group 400.
P
Confirm with the key "i/reset"
The display shows "run"
Confirm with the key "i/reset". The burner starts up.
The display shows all the phases and relative times in sequence.
The phases are listed in the section "List of phases" on page 17.
Phase 22:
Start of the fan motor.
Phase 24:
The burner goes to the pre-purging position, the air servomotor
opens the damper at 90°.
Phases 80, 81, 82, 83:
These phases relate to the valve seal test.
Phase 30:
The count of the pre-purging time pre-set in the factory begins.
Phase 36:
The burner goes to its switch-on position, point "P0", defined in
Tab. N on page 41: the display shows a flashing "P0" indication.
If the value proposed is adequate, confirm using the "+" but-
ton.
20107195
Start-up, calibration and operation of the burner
h min s
V
%
h
min
s
V
%
/reset
Otherwise, modify the ignition point (see the section"Procedure
for inserting and adjusting points on the modulation curve" on
page 39.
P
V
The values shown in the figure are purely for indi-
cation purposes.
WARNING
Phase 38:
The ignition phase begins and the spark goes off.
Phase 40:
The gas valves open (the count of the safety time begins). Using
the appropriate visor check there is a flame and that the combus-
tion parameters are correct. if necessary, vary the degrees of
opening/closing of the air and fuel servomotors.
If the control box goes into lockout, press the keys "+" and "-"
(ESC) simultaneously: the display visualises alternately the lock-
out code for flame absence c: 4) and the relative diagnostic (d:
3).
Solve the problem, referring to the paragraph "Ignition failure" on
page 49.
To unlock, see "Reset procedure" on page 36. The display visual-
ises "OFF Upr".
Repeat the "Start-up procedure".
The values previously inserted remain stored.
WARNING
Once the ignition has occurred (point "P0"), proceed with the
calibration of the modulation curve.
40
GB
h
min
s
%
P
V h
min
s
P
h
V
min s
%
%