6.6.1.5 Reset procedure
The burner is in lockout when the red indicator light on the oper-
ator panel is lit up, and the display visualises the lockout code (in
the example alongside c: 4 ) and the relative diagnostics (in the
example d: 3 ) alternately.
P
V h
P
V
To reset, press the "i/reset" key for 1 s: the display will show "rE-
SEt" . When the key is released, the lockout signal will disappear
and the red indicator light will switch off.
The control box is reset.
P
/reset
6.6.1.6 Manual lockout procedure
If necessary, it is possible to manually block the control box and,
consequently, the burner, by pressing the key "i/reset" simulta-
neously with any other key of the operator panel.
With the selector " 0-1 " (Fig. 33 at page 33), the
burner does not stop immediately, but the switch-
off phase is activated.
CAUTION
Start-up, calibration and operation of the burner
min
s
%
h
min s
%
V h
min
s
%
6.6.1.7 Manual operation procedure
After the adjustment of the burner and the setting of the points on
the modulation curve, it is possible to manually check the opera-
tion of the burner along the entire curve.
Example:
the burner is working at the requested load percentage: 20%.
P
Press the "F" key for 1 second: " LoAd" is displayed and the load
percentage flashes.
P
Releasing the "F" key, the standard visualisation appears, with
the current load percentage flashing: this means that the burner
is working in Manual mode (any outside adjustment is excluded
and only the safety devices are active).
P
Keep the "F" key pressed and, with the keys " +" or " –" , increase
or decrease the load percentage.
P
To exit manual mode, press the keys " + " and " - " ( ESC ) simulta-
neously for 3 seconds: the burner will work in Automatic mode
and the output will depend on the thermostat/adjustment pres-
sure switch (TR).