Fan Loss of
9
Phase
Loss of Fan
10
Motor Control
Fan Power
11
Module Over
Temperature
12
Fan Startup
13
Fault
14
15
0
1
2
3
4
1079
Fan Power
Module
5
Temperature
Low / Sensor
Fault
6
Emerson Classification:
Internal
61
© 2023 Emerson Climate Technologies, Inc.
1. Verify the correct fan motor has been selected.
2. Check the U, V, & W connections on the drive & fan
side.
1 2
3. Check the fan cable.
4. Check the fan motor windings.
1. Verify the correct fan motor has been selected.
2. Check the U, V, & W connections on the drive & fan
side.
3. Check the fan cable.
4. Check the fan motor windings.
1. Remove any obstructions to the condensing fan
motor.
2. Verify adequate airflow is supplied across heatsink of
the drive.
3. Check all the mounting screws on the drive, verify
they are all properly tightened.
4. If problem persists, replace the drive.
1. Verify the correct fan motor has been selected.
2. Verify there are no fan blade obstructions.
3. Check the U, V, & W, connections on the drive & fan
1
side.
4. Check the fan motor windings.
1. Verify ambient temperature is above the minimum
operating temperature of drive.
2. Power cycle drive.
3. If problem persists, replace drive