CLEANING

The Xact Count may
not count due to either the magnet shuttle or the spring hanging up inside the magnet
housing. The counter components can be cleaned by washing the unit in warm water. A soft brush may be used
to remove debris.
Tools required include:
1. 2x 1-7/16 end wrench or cresent wrench
2. 3/32 Allen key
To disassemble valve, follow these instructions:
1. Loosen set screw
2. Slide the collar off the valve housing (away from the retaining ring)
3. Disassemble valve body using the flats on the seat and body
4.
Use a soft bottle brush and warm water to clean any sediment on the inside of the valve and on any
internal components
5. Slide the spring back over the poppet shaft
6. Insert the poppet shaft into the guide hole in the body
7. Reassemble valve body and torque to 30ft-lbs
8. Slide counter and collar over valve body up to snap ring from the inlet end
9. Insert set screw into collar and torque to 15in-lbs
Figure 3: Counter Disassembly for Cleaning
PN: 95416
Operation Manual
XACT COUNT
REV 00
Page 7 of 12