Wiring Plan, Single Chamber Housing; Wiring Plan, Double Chamber Housing - Siemens SITRANS LG260 Operating Instructions Manual

Guided wave radar
Hide thumbs Also See for SITRANS LG260:
Table of Contents

Advertisement

Electronics and connec-
tion compartment
PBD-51041061
7. Check the hold of the wires in the terminals by lightly pulling on
them
8. Connect the screen to the internal ground terminal, connect the
external ground terminal to potential equalisation
9. Tighten the compression nut of the cable entry gland. The seal
ring must completely encircle the cable
10. Reinsert the display and adjustment module, if one was installed
11. Screw the housing lid back on
The electrical connection is finished.
5.3

Wiring plan, single chamber housing

The following illustration applies to the non-Ex, Ex-ia and Ex-d ver-
sion.
1
Fig. 10: Electronics and connection compartment - single chamber housing
1
Voltage supply, signal output
2
Contact pins for the display and adjustment module or interface adapter
3
Simulation switch ("1" = mode for simulation release)
4
For external display and adjustment unit
5
Ground terminal for connection of the cable screening
5.4

Wiring plan, double chamber housing

The following illustration applies to the non-Ex, Ex-ia and Ex-d ver-
sion.
SITRANS LG260 - Operating Instructions