Minimum Run Time; Recommended Inverter Range - Emerson Copeland 2D Application Manuallines

Semi-hermetic compressors for a2l & a1 applications
Hide thumbs Also See for Copeland 2D:
Table of Contents

Advertisement

Copeland 2D*, 3D* and 8D* compressors must be equipped with the correct accessories, according
to Emerson documentation and considering the application intended. Make sure this requirement is
met before start-up.
Bolt torque settings are listed in Appendix 2.
With the exception of rubber-coated metallic gaskets (Wolverine) all gaskets should be oiled before
fitting. O-rings should also be oiled.
NOTE: A compressor should never be operated beyond its approved application range!
Check by consulting the appropriate data sheet. To avoid motor damage, NEVER start the
compressor or carry out high-potential testing when the compressor is under vacuum.
5.6

Minimum run time

Emerson recommends a maximum of 10 starts per hour. The most critical consideration is the
minimum run time required to return oil to the compressor after start-up. The minimum on time
becomes the time required for oil lost during compressor start-up to return to the compressor sump.
Cycling the compressor for a shorter period than this, for instance to maintain very tight temperature
control, will result in progressive loss of oil and damage to the compressor.
5.7

Recommended inverter range

2D*, 3D* and 8D* semi-hermetic compressors are released for inverter applications. However, the
operation of semi-hermetic compressors with A2L refrigerants, eg, R454C, R455A or R454A and
variable frequency has not been officially qualified at this time.
Over a frequency range the compressor system combination can have frequency bands with higher
vibration. The degree of vibration and frequency bands are highly dependent on the system. To help
reduce these vibration levels rubber mounting can be used on all inverter-driven compressors.
Active oil management should be used for all inverter-driven compressors.
Copeland compressors are released for operation with frequency variations from 25 to 60 Hz.
26
AGL_HA_ST_Discus_A2L_A1_EN_Rev00

Advertisement

Table of Contents
loading

This manual is also suitable for:

Copeland 3dCopeland 8d

Table of Contents