DA PID Single Loop and Dual Loop Modules
Installation Guide
z Dedicated single and dual PID modules for the DA70
z Auto addressing minimizes configuration time
z Fully isolated design provides reliable operation
z PID control with reduced overshoot
z Universal inputs accept TC, RTD, 0-10 V and 0/4-20 mA
signals
z On demand auto-tuning of PID settings
z DC analog output (1PID only)
z Heater current input (optional, 2PID only) ensures detection
of heater circuit failure
z Configured using Crimson
U L
C
US
FOR USE IN HAZARDOUS LOCATIONS:
R
Class I, Division 2, Groups A, B, C, and D
LISTED
T4
IND.CONT. EQ.
E317425
MODULE PACKAGE CHECKLIST
This product package should contain the items listed below. If
any items are missing or damaged, contact Red Lion immediately.
- DIN rail mount DA PID Module
- Installation Guide
GENERAL DESCRIPTION
The DA PID modules are full featured PID controllers designed
for use with the DA70 controllers. The 1PID is a single loop
controller, while the 2PID is a dual loop controller. The design of
the system provides a true modular PID control platform for
multi-zone control applications. The modules can accept a wide
range of thermocouple, RTD, 0-10 V, 0/4-20 mA signals. With
multiple discrete outputs, plus an analog output (1PID only), the
DA PID modules can perform virtually any combination of time-
proportioning or linear control for heat, cool, or heat/cool
applications. The discrete outputs may also be assigned to one of
seven internal soft alarms. The 1PID's linear output can be
assigned to transmit virtually any internal variable.
The modules connect and communicate via proprietary
DIMENSIONS In inches (mm)
0.49
4.53 (114.97)
(12.51)
24
23
22
21
20
6.00
19
18
17
16
(152.40)
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
0.45
(11.50)
®
software (version 3.1 or later)
1.91
(48.51)
1.35
(34.32)
This
terminal
2PID only
6.22
(157.91)
II 3 G Ex ec IIC T4 Gc
DEMKO 20 ATEX 2268X
IECEx UL 20.0007X
For Part Numbers: DAM00PDP1SA00000,
DAM00PDP2S000000, and DAM00PDP2SM00000 Only
backplane to the DA host device. The DA host device, equipped
with serial ports as well as an Ethernet port(s), allows the system
to share data with PCs, PLCs, and SCADA systems.
Internal power management circuits allow the module to be
replaced while power is applied, which reduces downtime in the
event of a relay failure. All configuration information is stored
locally within the module, as well as in the Host, so replacement
modules do not need to be configured.
The modules can operate in On/Off, P, PI, or PID control mode,
and use an on-demand Auto-Tune that establishes the tuning
constants. The PID constants may be fine-tuned through the
serial or Ethernet interface. The modules employ a unique
overshoot suppression feature, which allows the quickest
response without excessive overshoot. The modules can also be
operated in manual mode, providing the operator with direct
control of the output.
CONFIGURATION
The DA PID modules are configured with Windows
®
Crimson
software. The software is an easy to use, graphical
interface which provides a means of configuration and
commissioning of new systems, as well as routine re-calibration
of modules.
ALARMS
Each loop within the modules has seven internal "soft" alarms,
which can be assigned to trigger any output. This includes four
process alarms, two heater current, and one input fault alarm.
ANALOG OUTPUT OPTION (1PID ONLY)
The DC Analog Output (10 V or 20 mA) can be independently
configured and scaled for control or re-transmission purposes.
HEATER CURRENT MONITOR OPTION (2PID ONLY)
The optional Heater Current Monitor input is useful for early
warning of heater degradation, or heater circuit failure. The input
1
Installation DAPID-A
Drawing No. LP1120
Effective 03/2020
®
compatible

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the DAM00PDP1SA00000 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Redlion DAM00PDP1SA00000

  • Page 1 LISTED IECEx UL 20.0007X IND.CONT. EQ. E317425 For Part Numbers: DAM00PDP1SA00000, DAM00PDP2S000000, and DAM00PDP2SM00000 Only MODULE PACKAGE CHECKLIST backplane to the DA host device. The DA host device, equipped with serial ports as well as an Ethernet port(s), allows the system This product package should contain the items listed below.
  • Page 2: Safety Summary

    Drawing No. LP1120 Effective 03 2020 connects to a current transformer with an output of 100 mA AC Normal Mode Rejection: >50 dB, 50/60 Hz ° to ensure that proper heater current is present when the control Temperature Coefficient: 0.01%/ output is on, and that little or no current is present when the Step Response Time: 100 msec typ., 200 msec max output is off.
  • Page 3: Control Modes

    IEC/EN 61010-1 time, derivative time values, and output dampening time RoHS Compliant ATEX Approved ( Probe Break Action: Programmable response DAM00PDP1SA00000, DAM00PDP2S000000, and DAM00PDP2SM00000 Only) Sensor Fail Response: Upscale II 3 G Ex ec IIC T4 Gc 12. ALARMS: DEMKO 20 ATEX 2268X...
  • Page 4: Emc Installation Guidelines

    Visit https:/ /www.redlion.net/emi for more information on EMI 4. Long cable runs are more susceptible to EMI pickup than guidelines, Safety and CE issues as they relate to Red Lion short cable runs.
  • Page 5: Hardware Installation

    Effective 03 2020 Drawing No. LP1120 HARDWARE INSTALLATION Installing Module into Cradle Push module into cradle until you hear an audible click Removing Module From Cradle indicating it is properly latched. To remove the module from the cradle, push in the module release button at the top of the cradle and pull the module out of the cradle.
  • Page 6: Input Wiring

    Drawing No. LP1120 Effective 03 2020 INPUT WIRING HCM (OPT) HCM (OPT) HCM (OPT) HCM (OPT) 4-20 mA 4-20 mA HCM (OPT) -10 V -10 V HCM (OPT) RTD +EXC RTD +EXC 4-20 mA TC/RTD+ TC/RTD+ -10 V INPUT COM INPUT COM RTD +EXC Heater Circuit...
  • Page 7: Ordering Information

    50 Amp Current Transformer (For Heater Current Models), Accessories UL Recognized component, Instrument Transformers, CT005001 Inc. Part #2SFT500-0. A listing of the entire DA70 family of products and accessories can be found at www.redlion.net. Module is not suitable for use in hazardous locations.