Viessmann VITODENS 100 Installation And Service Instructions Manual page 69

Gas fired wall mounted condensing boiler
Hide thumbs Also See for VITODENS 100:
Table of Contents

Advertisement

Fault finding
(cont.)
Display
System character-
fault code
istics
F3
Burner in fault state
F4
Burner in fault state
F5
Burner blocked
F7
Burner blocked
F8
Burner in fault state
F9
Burner in fault state
FA
Burner in fault state
Fd
Burner blocked
Cause
Measures
The flame signal
Check the ionisation
is already present
electrode and leads.
at burner start
Press"Reset".
No flame signal is
Check the ionisation
present
electrode and leads,
measure the ionisation
current, check the gas
pressure, check the gas
combination valve, igni-
tion, ignition module and
condensate drain.
Press"Reset".
Air pressure
Check the air pressure
switch faulty
switch and the intercon-
necting cable.
Faulty water pres-
Check the water pres-
sure sensor
sure sensor and the in-
terconnecting cable.
Fuel valve closes
Check gas combination
too late
valve. Check both con-
trol paths.
Press"Reset".
Fan speed too
Check the fan, check
low at burner start
the fan cables and sup-
ply, check the fan con-
trol.
Press"Reset".
Fan not at stand-
Check the fan, check
still
the fan cables, check
the fan control.
Press"Reset".
Burner control
Check the ignition elec-
unit fault
trodes and leads. Check
whether a strong inter-
ference (EMC) field ex-
ists near the equipment.
Press"Reset".
If the fault is not re-
moved, replace the con-
trol unit.
Troubleshooting
69