Carrier PG96MSA Installation, Start-Up, Operating And Service And Maintenance Instructions

Single-stage, high efficiency, 4-way multipoise 35-in. (889 mm), condensing gas furnace

Advertisement

PG96MSA
Single-Stage, High Efficiency, 4-Way Multipoise
35-in. (889 mm), Condensing Gas Furnace
NOTE: Read the entire instruction manual before starting the
installation.

TABLE OF CONTENTS

IMPORTANT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Table 1 - Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Table 2 - Minimum Clearances to Combustible Materials
for All Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Table 3 - Loose Parts Bag . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
CODES AND STANDARDS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS PROCE-
DURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
ACCESSORIES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
LOCATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
AIR FOR COMBUSTION AND VENTILATION . . . . . . . . . . . . . . 8
Table 4 - Minimum Free Area Required for Each Combustion Air
Opening or Duct to Outdoors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Table 5 - Minimum Space Volumes for 100% Combustion, Ventila-
tion and Dilution Air from Outdoors . . . . . . . . . . . . . . . . . . . . . . . 9
CONDENSATE TRAP. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
CONDENSATE DRAIN CONNECTION . . . . . . . . . . . . . . . . . . . . 13
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Table 6 - Opening Dimensions - In. (mm) . . . . . . . . . . . . . . . . . 18
FILTER ARRANGEMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Table 7 - Filter Media Pressure Drop (Clean) Versus Airflow - in. w.c.
(Pa) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Table 8 - Filter Media Pressure Drop (Clean) Versus Face Velocity-
in. w.c. (Pa) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Table 9 - Air Filter Selection and Duct Sizing - In. (mm) . . . . . 21
AIR DUCTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
GAS PIPING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Table 10 - Maximum Capacity of Pipe . . . . . . . . . . . . . . . . . . . . 23
ELECTRICAL CONNECTIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Table 11 - Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
37) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
VENTING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Table 12 - Vent Termination Kit for Direct Vent (2-pipe) Systems29
Table 13 - Approved Combustion-Air and Vent Pipe, Fitting and Ce-
ment Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Table 14 - Maximum Equivalent Vent Length - Ft. . . . . . . . . . . 40
Table 15 - Deductions from Maximum Equivalent Vent Length - Ft.
(M) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Table 16 - Maximum Allowable Exposed Vent Length in Uncondi-
tioned Space - Ft. / M. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Portions of the text and tables are reprinted from NFPA 54/ANSI Z223.1E, with permission of National Fire Protection Association, Quincy, MA
02269 and American Gas Association, Washington DC 20001. This reprinted material is not the complete and official position of the NFPA or ANSI
Installation, Start-up, Operating and
Service and Maintenance Instructions
on the referenced subject, which is represented only by the standard in its entirety.
Table 17 - Hanger Spacing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
AIR DELIVERY - CFM. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Table 18 - Air Delivery - CFM (with filter) . . . . . . . . . . . . . . . . 48
Table 19 - Airflow Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
AND NAVIGATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Table 20 - System Status Display Codes . . . . . . . . . . . . . . . . . . 52
Table 21 - Main Menu Options . . . . . . . . . . . . . . . . . . . . . . . . . . 52
SERVICE LABEL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Table 22 - Test Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
ADJUSTMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Table 23 - Altitude Derate Multiplier for U.S.A. . . . . . . . . . . . . 57
Table 24 - Gas Rate (CU ft./hr). . . . . . . . . . . . . . . . . . . . . . . . . . 58
Table 25 - Orifice Size and Manifold Pressure (in. w.c.) for Gas Input
Rate - 40,000 BTUh to 140,000 BTUh . . . . . . . . . . . . . . . . . . . . 59
Table 26 - Orifice Size and Manifold Pressure (in. w.c.) for Gas Input
Rate - 26,000 BTUh ONLY. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
SERVICE AND MAINTENANCE PROCEDURES. . . . . . . . . . . . 61
ELECTRICAL CONTROLS AND WIRING . . . . . . . . . . . . . . . . . 61
CARE AND MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
WINTERIZATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
SEQUENCE OF OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
TROUBLSHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
PARTS REPLACEMENT INFORMATION GUIDE . . . . . . . . . . . 73
MODEL NOMENCLATURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
To learn more about this appliance and installation via a mobile device,
go to
https://www.CAC/BDP.com/NFC
access airflow tables or troubleshooting guide on your mobile device go
to
mlctraining.com/training/techdocs/39/
or use the QR code below. To
or use the QR code below.
A220936
A200352

Advertisement

Table of Contents
loading

Summary of Contents for Carrier PG96MSA

  • Page 1: Table Of Contents

    PG96MSA Single-Stage, High Efficiency, 4-Way Multipoise 35-in. (889 mm), Condensing Gas Furnace Installation, Start-up, Operating and Service and Maintenance Instructions NOTE: Read the entire instruction manual before starting the Table 17 – Hanger Spacing ......46 installation.
  • Page 2: Required Notice For Massachusetts Installations

    PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions REQUIRED NOTICE FOR MASSACHUSETTS INSTALLATIONS IMPORTANT The Commonwealth of Massachusetts requires compliance with regulation 248 CMR as follows: 5.08: Modifications to NFPA-54, Chapter 10 2) Revise 10.8.3 by adding the following additional requirements: a.
  • Page 3 PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions A210796 Fig. 1 – Dimensional Drawing Table 1 – Dimensions SHIP WT. FURNACE SIZE LB (KG) CABINET WIDTH OUTLET WIDTH BOTTOM INLET WIDTH AIR INTAKE 30026A 14-3/16 (361) 12-1/2 (319) 12-9/16 (322)
  • Page 4: Safety Considerations

    PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions SAFETY CONSIDERATIONS WARNING WARNING FIRE, INJURY, OR DEATH HAZARD Failure to follow this warning could result in property damage, personal FIRE, INJURY, OR DEATH HAZARD injury, or death. Failure to follow this warning could result in property damage, personal Do not bypass any of the safety controls in the furnace, including but injury, or death.
  • Page 5: For All Units

    PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions Understand the signal words DANGER, WARNING, and CAUTION. MUST be used when installed on combustible materials and wood These words are used with the safety-alert symbol. DANGER identifies flooring. Special base is not required when this furnace is installed the most serious hazards which will result in severe personal injury or on manufacturer’s cased evaporator coils or when manufacturer’s...
  • Page 6: Codes And Standards

    PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions A150573 Fig. 3 – Freeze Protection and Return Air Temperature The furnace should be sized to provide 100 percent of the design heating A12182 Fig. 4 – Prohibited Installations load requirement plus any margin that occurs because of furnace model WARNING size capacity increments.
  • Page 7: Dure

    PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions General Installation 2. Firmly touch the clean, unpainted, metal surface of the furnace chassis which is close to the control. Tools held in a person’s hand • US: NFPA 54/ANSI Z223.1 and the NFPA 90B. For copies, contact during grounding will be satisfactorily discharged.
  • Page 8: Air For Combustion And Ventilation

    PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions All fuel-burning equipment must be supplied with air for fuel WARNING combustion. Sufficient air must be provided to avoid negative pressure in the equipment room or space. A positive seal must be made between...
  • Page 9 PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions least 50 cubic feet per 1,000 BTUh input rating for all gas appliances CAUTION installed in the space. • Spaces having less than 50 cubic feet per 1,000 BTUh (4.8 cubic FURNACE CORROSION HAZARD meters per kW) require the Outdoor Combustion Air Method.
  • Page 10 PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions Indoor Combustion Air© NFPA & AGA Standard and Known-Air-Infiltration Rate Methods Indoor air is permitted for combustion, ventilation, and dilution, if the Standard or Known-Air-Infiltration Method is used. WARNING CARBON MONOXIDE POISONING HAZARD Failure to follow this warning could result in personal injury or death.
  • Page 11: Condensate Trap

    PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions openings in doors or floors having free area of at least 2 furnace is installed in the downflow orientation, the condensate trap in.2/1,000 BTUh (4,400 mm2/kW) of total input rating of all gas must be relocated for proper condensate drainage.
  • Page 12 PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions A230047 Fig. 10 – Horizontal Right Trap Configuration (Appearance may vary) A170135 Fig. 12 – Example of Field Drain Attachment To Relocate the Condensate Trap: • Orient the furnace in the downflow position.
  • Page 13: Condensate Drain Connection

    PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions CONDENSATE DRAIN CONNECTION Evaporator Coil + + + CAUTION + = Positive pressure < + = Pressure lower than areas with + = Negative pressure Condensing PROPERTY DAMAGE HAZARD Furnace Blower creates positive pressure.
  • Page 14 PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions 4. From inside the casing, insert the formed grommet end of the elbow The remaining drain line can be constructed from field supplied 1/2-in. through the 7/8-in. hole in the casing.
  • Page 15 PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions condensate and compatible with mineral and vegetable oils, such as canola oil. Allow at least 1/4-in. per foot (20 mm per meter) of slope down and away from the furnace in horizontal sections of drain line.
  • Page 16: Installation

    PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions Return Air Connections WARNING FIRE HAZARD A failure to follow this warning could cause personal injury, death and/or property damage. Never connect return-air ducts to the back of the furnace. Follow instructions below.
  • Page 17 PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions 4. If downflow subbase is used, install as shown. If manufacturer’s cased evaporator coil or coil casing is used, install as shown in Fig. NOTE: It is recommended that the perforated supply-air duct flanges be completely removed from furnace when installing the furnace on a factory-supplied cased coil or coil box.
  • Page 18 PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions Bottom Return Air Inlet flanges or air conditioning coil casing (when used). DO NOT cut main furnace casing side to attach supply air duct, humidifier, or other These furnaces are shipped with bottom closure panel installed in bottom accessories.
  • Page 19: Filter Arrangement

    PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions NOTICE FURNACE FURNACE (OR COIL CASING WHEN USED) APPROVED COIL ASSEMBLY Design the duct system FIRST to determine how much pressure drop COIL BOX may be allowed in the filter system. See the Air Ducts section.
  • Page 20 PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions Table 7 – Filter Media Pressure Drop (Clean) Versus Airflow - in. w.c. (Pa) Factory-Accessory Representative After-Market Filter Media 14 x 25 Filter Factory-Accessory (356 x 635 mm) Washable Media Fiberglass Pleated (1-in.
  • Page 21 PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions Table 9 – Air Filter Selection and Duct Sizing - In. (mm) COMBUSTION-AIR PIPE (SEE VENTING SECTION) FILTER SIZE FURNACE CASING FILTER TYPE SIDE BOTTOM WIDTH RETURN RETURN 16 x 25 x 3/4...
  • Page 22: Air Ducts

    PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions Location Relative to Cooling Equipment Maintain a 1-in. (25 mm) clearance from combustible materials to supply air ductwork for a distance of 36-in. (914 mm) horizontally from The cooling coil must be installed parallel with, or on the downstream the furnace.
  • Page 23 PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions Table 10 – Maximum Capacity of Pipe CAUTION 1-1/4 1-1/2 Nominal: 1/2 (12.7) 3/4 (19.0) 1 (25.4) (31.8) (38.1) FURNACE DAMAGE HAZARD Actual ID: 0.622 0.824 1.049 1.380 1.610 Failure to follow this caution may result in furnace damage.
  • Page 24: Electrical Connections

    PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions ELECTRICAL CONNECTIONS SUPPLY WARNING FRONT ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARD MANUAL SHUT OFF Failure to follow safety warnings could result in dangerous operation, VALVE (REQUIRED) serious injury, death or property damage.
  • Page 25 PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions FIELD 24-V WIRING FIELD 115-, 208/230-, 460-V WIRING FACTORY 24-V WIRING FACTORY 115-V WIRING NOTE 2 THERMOSTAT ELECTRIC FIVE WIRE FIELD-SUPPLIED TERMINALS DISCONNECT DISCONNECT THREE-WIRE SWITCH HEATING-ONLY 208/230- OR COPPER BLOWER DOOR SWITCH...
  • Page 26 PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions 2. Drill two (2) 1/8-in. (3 mm) pilot holes through the dimples in the furnace casing near the 7/8-in. hole. For a side-mounted external electrical box, complete the following: 1. Align the J-Box bracket with the 7/8-in. (22 mm) hole inside the furnace casing.
  • Page 27: Accessories (See Fig. 37)

    PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions 4. Pull furnace power wires through 1/2-in. (12 mm) diameter hole in similar device. See humidity sensing thermostat, zone controller, J-Box. If necessary, loosen power wires from strain—relief wire-tie thermostat, or controller manufacturer’s instructions for proper on furnace wiring harness.
  • Page 28: Venting

    PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions 8. Thermostat terminal connection order on furnace control may vary- THERMOSTAT reference furnace control labeling for designations NOTICE OPTIONAL VENTING BELOW THE FURNACE The venting system may be positioned below the furnace ONLY IF the factory accessory External Vent Trap Kit is used.
  • Page 29 PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions The authority having jurisdiction (gas inspection authority, municipal utilisé avec les Royal Pipe. Système IPEX 636, apprêt PVC/CPVC, building department, fire department, etc.) should be consulted before Purple pour évacuation des gaz de combustion et système IPEX 636(1)t, installation to determine the need to obtain a permit.
  • Page 30 PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions Table 13 – Approved Combustion-Air and Vent Pipe, Fitting and Cement Materials MATERIALS 1. All pipe*, fittings*, primers**, and solvents** must conform to American National Standards Institute (ANSI) standards and American Society for Testing and Materials (ASTM) standards 2.
  • Page 31 PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions These furnaces can be vented as direct-vent (two-pipe), ventilated WARNING combustion air or non-direct (single-pipe) vent system. Each type of venting system is described below. Common venting between these CARBON MONOXIDE POISONING HAZARD furnaces or other appliances is prohibited.
  • Page 32 PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions 12 in. (305mm) min. separation between bottom of combustion air and bottom of vent (Typ.) A13305 Fig. 39 – Combustion Air and Vent Pipe Termination for Direct Vent (2-Pipe) System A05091 Fig.
  • Page 33 PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions A190032 Fig. 41 – Inside Corner Termination Inside Corner Terminations Inside corner vent terminations are permitted provided that: • Only two exterior walls come together to form an angle of 90 degrees to 135 degrees. There are no other exterior walls attached to either wall to form an alcove.
  • Page 34 PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions A12326 Fig. 42 – Direct Vent Termination Clearance NOTE: The following is based upon National codes for gas appliances and is provided as a reference. Refer to local codes which may supersede these standards and/or recommendations.
  • Page 35 PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions A12325 Fig. 43 – Ventilated Combustion Air and Non-Direct Vent Termination Clearance NOTE: The following is based upon National codes for gas appliances and is provided as a reference. Refer to local codes which may supersede these standards and/or recommendations.
  • Page 36 PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions 2. The vent termination must be located at least 3 feet from an inside WARNING corner and follow the clearance distances in the Inside Corner Termination drawing. See Fig. CARBON MONOXIDE POISONING HAZARD 3.
  • Page 37 PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions and/or five feet of pipe may be used to accomplish the sound attenuation function. Ventilated Combustion Air intake pipe WARNING Pipe hangar CARBON MONOXIDE POISONING HAZARD 3” (76 mm) Failure to follow the instructions outlined below for each appliance being placed into operation could result in carbon monoxide poisoning or death.
  • Page 38 PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions Table 14 minus the number of fittings multiplied by the deduction for each type of fitting used from Table FURNACE NOT IN HORIZONTAL SECTION PIPE DIAMETER TRANSITION IN VERTICAL SECTION A93034 Fig.
  • Page 39 PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions 4. If a Tee is used on the termination (Alberta and Saskatchewan, when required) record the equivalent length of the Tee used. 5. Calculate Total Equivalent Vent Length by adding the equivalent lengths of the fittings to the lengths of the individual vent and combustion air pipes.
  • Page 40 PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions Table 14 – Maximum Equivalent Vent Length - Ft. NOTE: Maximum Equivalent Vent Length (MEVL) includes standard and concentric vent termination and does NOT include elbows. Table 15 - Deductions from Maximum Equivalent Vent Length to determine allowable vent length for each application.
  • Page 41 PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions Combustion Air and Vent Piping Insulation Guidelines NOTE: Use closed cell, neoprene insulation or equivalent. The vent pipe may pass through unconditioned areas. The amount of Slope vent pipe back to the furnace at least ¼”...
  • Page 42 PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions A230011 UPFLOW VERTICAL VENT Fig. 53 – Upflow Configurations (Appearance may vary) See “Notes for Venting Options” Requires Accessory Internal Vent Kit. See Product Data for current kit number. A11313A DOWNFLOW VERTICAL Fig.
  • Page 43 PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions A11329A A11336 HORIZONTAL LEFT-RIGHT VENT CONFIGURATION HORIZONTAL RIGHT-LEFT VENT CONFIGURATION Fig. 55 – Horizontal Left (Appearance may vary) See “Notes for Venting Options” A11337 HORIZONTAL RIGHT-VERTICAL VENT CONFIGURATION A11335 HORIZONTAL RIGHT-RIGHT VENT CONFIGURATION Fig.
  • Page 44 PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions 40,000* BTUh 60,000 BTUh Unit 3/8-in. 1/2-in. Size Uninsulated Uninsulated 3/8-in. Insulation 1/2-in. Insulation Insulation Insulation Winter Pipe Design 1 ½ 2 ½ 1 ½ 2 ½ 1 ½ 2 ½...
  • Page 45 PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions 100,000 BTUh Unit Size Uninsulated 3/8-in. Insulation 1/2-in. Insulation Pipe Winter Dia. mm Design 15.2 12.2 10.7 24.4 28.9 24.4 24.4 32.0 27.4 Temp °C 16.8 13.7 10.7 19.8 16.7 13.7 10.7...
  • Page 46 PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions mark. Quickly apply approved cement to end of pipe and fitting KGAVT0801CVT. For two-pipe or single pipe vent systems, a flashing socket (over primer). Apply cement in a light, uniform coat on for each pipe of the required diameter will be necessary.
  • Page 47 PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions 4. Locate assembly through sidewall with rain shield positioned no 4. Disassemble loose pipe fittings. Clean and cement using same more than 1-in. (25 mm) from wall as shown in Fig.
  • Page 48: Air Delivery - Cfm

    PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions Example 2 A direct-vent 60,000 BTUh furnace installed at 2100 ft. (640M). Venting system includes FOR EACH PIPE: 100 feet (30 M) of vent pipe, 95 feet (29 M) of combustion air inlet pipe, (3) 90º long-radius elbows, and a polypropylene concentric vent kit. Also includes 20 feet (6.1 M) of flexible polypropylene vent pipe, included within the 100 feet (30 M) of vent pipe.
  • Page 49 PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions Table 18 – Air Delivery - CFM (with filter) (Continued) External Static Pressure (IN.W.C.) Airflow Default Unit Size Setting Setting Cont. Fan Heat 36040B 1030 1085 1050 1020 1140 1105 1080...
  • Page 50 PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions Table 18 – Air Delivery - CFM (with filter) (Continued) External Static Pressure (IN.W.C.) Airflow Default Unit Size Setting Setting Cont. Fan 1005 1070 1025 1145 1100 1060 1020 48080B 1215...
  • Page 51 PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions Table 18 – Air Delivery - CFM (with filter) (Continued) External Static Pressure (IN.W.C.) Airflow Default Unit Size Setting Setting Cont. Fan 1060 1145 1070 1250 1175 1105 1025 1345 1280...
  • Page 52: Furnace Control Programming

    PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions FURNACE CONTROL PROGRAMMING This furnace model is equipped with an on-board 3-digit LCD display with pushbutton navigation for the adjustment of operating parameters, AND NAVIGATION diagnostics, and service. The control board must be powered to use the On-Board Control Method display and pushbuttons.
  • Page 53 PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions Control Board Replacement Further details and instructions for these programming methods are provided with the replacement control board. If the control board must be replaced, the new board must be programmed with the correct Model Program Number before the furnace CAUTION will operate.
  • Page 54: Service Label

    PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions SERVICE LABEL Scroll through main menu by pressing the MENU/SELECT button. Scan QR code or reference troubleshooting guide in installation manual. The major status code is displayed in the first 2 digits of the display. The minor status Press NEXT/OPTION button to view current setting (will flash on code is displayed in the third digit .
  • Page 55: Wiring Diagram

    PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions c. To initiate the component test sequence, the control must be in CAUTION (idL) mode no thermostat demands (W, Y, G). Select component test (Ct) from menu select buttons to start the component test SHOCK HAZARD sequence.
  • Page 56: Adjustments

    PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions Prime Condensate Trap with Water WARNING WARNING FIRE OR EXPLOSION HAZARD CARBON MONOXIDE POISONING HAZARD Failure to follow this warning could result in personal injury, death, and/or property damage. Failure to follow these warnings could result in personal injury or death.
  • Page 57 PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions 2. Obtain average yearly gas specific gravity from local gas supplier. NOTICE 3. Find installation altitude in Table 25 Table 4. Find closest natural gas heat value and specific gravity in...
  • Page 58 PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions 1. Adjust manifold pressure to obtain proper gas input rate. See Fig. a. Refer to the correct manifold pressure table for the appropriate model. b. Turn gas valve ON/OFF switch to OFF.
  • Page 59: Rate - 26,000 Btuh Only

    PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions Table 24 – Gas Rate (CU ft./hr) (Continued) SINGLE-STAGE FURNACE (TABULATED DATA BASED ON 20,000 BTUH PER BURNER, DERATED 2%/1000 FT (305M) ABOVE SEA LEVEL) ALTITUDE RANGE HEAT VALUE 0.58 0.60 0.62...
  • Page 60 PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions exchangers so that radiant heat does not affect thermometer readings. This is particularly important with straight run ducts. 2. When thermometer readings stabilize, subtract return-air temperature from supply-air temperature to determine temperature rise.
  • Page 61: Service And Maintenance Procedures

    PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions Check Safety Controls CAUTION The flame sensor, gas valve, and pressure switch were all checked in the Start-up procedure section as part of normal operation. ENVIRONMENTAL HAZARD 1. Check Main Limit Switch Failure to follow this caution may result in environmental pollution.
  • Page 62: Care And Maintenance

    PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions (Light-Emitting Diode) and Major/Minor 3 digit codes to aid in WARNING installation, servicing, and troubleshooting. Status codes can be viewed at the sight glass in blower access door. The furnace control LED is ELECTRICAL SHOCK AND FIRE HAZARD either ON continuously, rapid flashing, or a code composed of 2 digits.
  • Page 63 PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions 4. If the vent and combustion air pipe passes through the blower WARNING compartment, it will be necessary to remove the pipes from the blower compartment. CARBON MONOXIDE POISONING AND FIRE...
  • Page 64 PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions Cleaning Burners and Flame Sensor The following items must be performed by a qualified service technician. If the burners develop an accumulation of light dirt or dust, they may be cleaned by using the following procedure:...
  • Page 65 PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions 18. Install control door when complete. BURNER SUPT. ASSY IGNITER BRACKET, IGNITER BURNER ASSY 1-1/4-in. (31.8) 2-1/2-in. (64.4) A11405 Fig. 67 – Igniter Position - Top View FLAME ROLLOUT SWITCH FLAME SENSOR...
  • Page 66 PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions 2. Remove control door. 20. Connect the leads of the condensate heat pad (if used) 3. Disconnect pressure switch tube from pressure switch port. 21. Connect external drain piping to the condensate drain elbow or drain extension pipe.
  • Page 67: Winterization

    PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions Secondary Heat Exchangers WARNING The condensing side (inside) of the secondary heat exchanger CANNOT be serviced or inspected without complete removal of the heat exchanger FIRE OR EXPLOSION HAZARD assembly. Detailed information on heat exchanger removal can be Failure to follow this warning could result in personal injury, death, obtained from your Distributor.
  • Page 68 PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions diagram in Fig. 60, follow the sequence of operation through the 2. Cooling Mode different modes. Read and follow the wiring diagram very carefully. The thermostat “calls for cooling.” The thermostat closes the R-to-Y circuits. The R-to-Y circuit starts...
  • Page 69: Troublshooting

    PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions TROUBLSHOOTING A221116 Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
  • Page 70 PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions A221119 Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
  • Page 71 PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions A221120 Fig. 70 – Troubleshooting Guide Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
  • Page 72 PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions A230014 Fig. 71 – Gas Furnace Checklist Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
  • Page 73: Parts Replacement Information Guide

    PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions PARTS REPLACEMENT INFORMATION GUIDE Casing Group Filter Group Blower door Filter(s) Bottom plate Media Cabinet (when used) Gas Control Group Control door Door knob assembly Burner Top filler plate Flame sensor...
  • Page 74 PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions © 2023 Carrier. All rights reserved. Edition Date: 03/23 Catalog No: IM-PG96MSAA-01 REV C A Carrier Company Replaces: IM-PG96MSAA-01 REV B Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

Table of Contents