5-6. Reactor assy

Check point 1. Appearance check
No fissures, breaks, damage, etc. at the body and winding section, terminals section?
Check point 2. Electric check
Set the tester to the "Resistance" mode, and check for open/short between both ends of the
reactor wire (or connector).
Judge the result of 1. as follows:
Short
Normal
Open
Abnormal (open)
5-6. Reactor assy
NOTE: Reference value of DC resistance of reac-
tor used:
07-12 models: 408.0 mΩ (at 20°C), 14
model: 415.9 mΩ (at 25°C)