Attachment and installation cooling units multi controller (mc) – 400 / 460 v, 3~ (76 pages)
Summary of Contents for Pfannenberg DTS 8000ES
Page 1
All manuals and user guides at all-guides.com 外挂式机柜空调操作及使用说明书 DTS 8000ES 系列 Operating and assembly instruction For side-mounted cooling units DTS 8000ES 685408023V0.1...
Page 4
All manuals and user guides at all-guides.com 1 Hints on the manual ............................23 2 Handling ................................23 2.1 Transport ..............................23 2.2 Storage ................................. 23 2.3 Unpacking ..............................24 3 Scope of delivery and options ..........................24 4 General Information ............................24 5 Name plate .................................
Page 5
All manuals and user guides at all-guides.com 11.2 Operation display ............................37 11.3 Start-up / Test mode ..........................38 11.4 Door contact .............................. 38 11.5 Equipment fault ............................38 12 Parameters View and Settings .......................... 39 13 Cleaning and Maintenance ..........................40 13.1 Cleaning ..............................
All manuals and user guides at all-guides.com 8.4 气流原理 在安装此设备前应当完整仔细地阅读此说明。此说明是设备不可分割的一部分,在设备报废请前务必保留。 安装前,请确认设备间以及设备至墙体的距离至少有 200 毫米的间距;在柜子内部的进风口以及出风口没有干 涉以及障碍。 8.5 技术参数 685408023V0.1...
Page 14
All manuals and user guides at all-guides.com 性能 DTS 8041ES 制冷能力 A35/A35 * 800 / 880 W 制冷能力 A50/A35 * 550 / 615 W 冷媒* R 134a 冷媒量* 300 g 温控(工厂设置) +35°C (+95°F) 内部温度报警指示(工厂设置) > +50°C (+122°F) 环境温度 +15°C (+59°F) . . . +55°C (+131°F) 内部温度...
Page 15
All manuals and user guides at all-guides.com 性能 DTS 8241ES 制冷能力 A35/A35 * 1000 / 1100 W 制冷能力 A50/A35 * 870 / 955 W 冷媒 * R 134a 冷媒量* 340 g 温控(工厂设置) +35°C (+95°F) 内部温度报警指示(工厂设置) > +50°C (+122°F) 环境温度 +15°C (+59°F) . . . +55°C (+131°F) 内部温度...
Page 16
All manuals and user guides at all-guides.com 性能 DTS 8341ES 制冷能力 A35/A35 * 1500/1650 W 制冷能力 A50/A35 * 1070/1180 W 冷媒 * R 134a 冷媒量 * 370 g 温控(工厂设置)) +35°C (+95°F) 内部温度报警指示(工厂设置) > +50°C (+122°F) 环境温度 +15°C (+59°F) . . . +55°C (+131°F) 内部温度...
1 Hints on the manual This handbook contains instructions for the installation and operation of door or side-mounted, bolt-on Cooling Units provided by Pfannenberg. In this manual, safety recommendations and other information are structured as follows. If the measures described in the following are not strictly observed there is danger to life and health.
Any damage must be reported immediately to the forwarding agent ). Moreover, the latest edition of the "Pfannenberg After Sales Service Declaration" shall apply. •Before disposing of packing material ensure that it does not contain any loose components. urr caused by production may be present on the metal edges of the unit. Always wear protective gloves when carrying out maintenance work and installation.
All manuals and user guides at all-guides.com 6 Safety Cooling units produced by Pfannenberg are designed for use in dissipating heat from switch cabinets (IP 54). The cooling unit is only suitable for installing on the stationary operation. Only the authorized specialist can work on the cooling system and electrical components.
All manuals and user guides at all-guides.com 7.2 Operating principles The compressor (1) compresses the refrigerant until high pressure is achieved. During this process temperature increases. In the condenser (2) heat is dissipated to ambient air, the coolant becoming liquid. The condenser fan (5) takes ambient air in through the condenser, and then it releases the air.In the expansion valve (3) the pressure of the coolant drops.
All manuals and user guides at all-guides.com 8.2 Spare parts Please order your spare parts only with the Pfannenberg-parts-number. Spare parts DTS 8041ES DTS 8241ES DTS 8341ES 18861100018 18861100019 18861100020 Internal fan 18861100019 18861100020 18861100020 External fan 18860200025 18860200026 18860200026...
Page 30
All manuals and user guides at all-guides.com DTS 8041ES 685408023V0.1...
Page 31
All manuals and user guides at all-guides.com DTS 8241/8341ES 685408023V0.1...
All manuals and user guides at all-guides.com 8.4 Airflow principle Read this manual completely and carefully before installing the unit. Prior to mounting, ensure that the clearance of the units to each other and to the wall is at least 200mm; air inlet and outlet are not obstructed on the inside of the enclosure.
Page 33
All manuals and user guides at all-guides.com Cooling data DTS 8041ES Cooling capacity at A35/A35 * ** Q 800 / 880 W Cooling capacity at A50/A35 * ** Q 550 / 615 W Refrigerant type* R 134a Refrigerant amount* 300 g Thermostat setting, (factory set) +35°C (+95°F) Failure indication: Enclosure internal temp.
Page 34
All manuals and user guides at all-guides.com Cooling Data DTS 8241ES Cooling capacity at A35/A35 * 1000 / 1100 W Cooling capacity at A50/A35 * 870 / 955 W Refrigerant type * R 134a Refrigerant amount * 340 g Thermostat setting, (factory set) +35°C (+95°F) Failure indication: Enclosure internal temp.
Page 35
All manuals and user guides at all-guides.com Cooling data DTS 8341ES Cooling capacity at A35/A35 * 1500/1650 W Cooling capacity at A50/A35 * 1070/1180 W Refrigerant type * R 134a Refrigerant amount * 390 g Thermostat setting, (factory set) +35°C (+95°F) Failure indication: Enclosure internal temp.
All manuals and user guides at all-guides.com *ID Plate Information, ** Cooling capacity without filter mats (option) °) free-blowing, °°) need additional electrical terminal space 40mm 9 Installations 9.1 General •For effective cooling & ventilation , correct installation & ventilation of the cooling unit is very important. •The distance must be kept at least 200mm between units or the unit to the wall.
All manuals and user guides at all-guides.com 1 Cooling unit DTS 5 springs shim 2 switch cabinet wall or door 6 nuts 3 thread rod 7 bolts 4 flat gasket 8,9,10,11,12 sealing strip 5) If M8 bolts on the top of unit being removed during insatallation, rescew them back to the unit tightly after installation.
All manuals and user guides at all-guides.com The cooling unit may be damaged if the voltage is too high. It’s nominal voltage is 230V or 400V. 10 Operating condition •The voltage must be within ± 10% of the value indicated. •The frequency must be within ±3Hz of the value indicated.
All manuals and user guides at all-guides.com 11.3 Start-up / Test mode The cooling unit does not work if the door switch is open. Each time the unit is power-on (when the door switch is closed), the unit performs a start-up process lasting around 3 seconds which is followed by a test mode lasting around 110 seconds.
All manuals and user guides at all-guides.com will open the failure contact and the alarm code will be shown on the display. (See Section 15 for trouble shooting). The installation of the fault signal line is not subject to any special requirement. The contact may be loaded with max230V, 1A 12 Parameters View and Settings Parameters of cooling unit can be monitored and set via operation display.
All manuals and user guides at all-guides.com 13 Cleaning and Maintenance Please cut off the cooling unit’s power before carrying out any cleaning or maintenance operation. 13.1 Cleaning The operation efficiency and reliability of the equipment will be improved by periodic cleaning and maitenance, call our service team for further service cooperation.
All manuals and user guides at all-guides.com persons cannot start the cooling unit. When the cooling unit is no longer needed, it must be disposed of by authorized personnel in accordance with all applicable environmental protection regulations. (See section 4) 15 Trouble shooting In spite of careful maintenance, the equipment may still have a failure sometime in the future.
Page 43
All manuals and user guides at all-guides.com In order to maintain your warranty rights please observe the following when returning the unit; •Enclose an exact description of the fault in the shipping package. •Enclose proof of delivery (delivery note or copy of invoice). •Return the unit together with all accessories;use the original packaging or packaging of equivalent quality, send the unit freight prepaid and covered by an adequate transport insurance.
Page 44
All manuals and user guides at all-guides.com 685408023V0.1...
Need help?
Do you have a question about the DTS 8000ES and is the answer not in the manual?
Questions and answers