IV−Charging
WARNING
Refrigerant can be harmful if it is inhaled. Refrigerant
must be used and recovered responsibly.
Failure to follow this warning may result in personal
injury or death.
A−12CHP
For maximum performance of this heat pump system, the
operating temperatures and pressures should be checked
and superheat determined at Standard ARI test conditions
of 82_F outdoor − 80_F indoor dry bulb/67_F wet bulb. If su-
perheat measured deviates from values in table 6, refriger-
ant charge should be adjusted accordingly for maximum
performance.
Verify system performance using table 7 or table 8 as a gen-
eral guide. These tables should not be used for charging the
unit. Minor variations in these pressures may be expected
due to differences in installations. Significant differences
70°F db RETURN AIR
MODEL
PRESSURE
12CHP−024
12CHP−030
12CHP−036
SUCTION
SUCTION
12CHP−042
12CHP−048
12CHP−060
12CHP−024
12CHP−030
12CHP−036
LIQUID
LIQUID
12CHP−042
12CHP−048
12CHP−060
80°F db / 67°F wb RETURN AIR
MODEL
PRESSURE
12CHP−024
12CHP−030
12CHP−036
SUCTION
SUCTION
12CHP−042
12CHP−048
12CHP−060
12CHP−024
12CHP−030
12CHP−036
LIQUID
LIQUID
12CHP−042
12CHP−048
12CHP−060
TABLE 7
NORMAL OPERATING PRESSURES −− HEATING MODE
AIR TEMPERATURE ENTERING OUTDOOR COIL (°F)
10°
15°
17
20
24
28
14
17
21
25
14
17
21
25
16
19
23
27
15
18
22
26
14
17
21
25
181
191
200
209
168
173
179
184
165
172
178
184
167
174
181
187
203
211
220
229
163
170
177
183
TABLE 8
NORMAL OPERATING PRESSURES −− COOLING MODE
AIR TEMPERATURE ENTERING OUTDOOR COIL (°F)
65°
70°
75°
80°
78
79
81
82
78
79
81
82
75
77
80
82
80
81
82
84
78
79
80
82
78
79
80
82
140
155
170
184
145
159
173
187
146
161
176
191
155
170
185
200
164
180
196
213
166
182
198
214
Page 17
could mean that the system is not properly charged or that a
problem exists with some component in the system. Used
carefully, this table could serve as a useful service guide.
Table 7 should be used when unit is charged during the
heating mode. If outdoor ambient is below 45°F, run unit
through defrost cycle first, wait 15 minutes for system pres-
sures to stabilize, then take pressures. Data in table 7 is
based on 70°F dry bulb return air. Data in table 8 is based
on 80°F dry bulb / 87°F wet bulb return air. Allow unit opera-
tion to stabilize before taking pressure readings.
12CHP SUCTION SUPERHEAT TABLE
UNIT MODEL NO.
12CHP−024
12CHP−030
12CHP−036
12CHP−042
12CHP−048
12CHP−060
20°
25°
30°
35°
33
38
43
49
29
34
39
45
29
34
39
45
31
36
41
45
30
35
40
45
29
34
39
44
219
228
237
247
189
195
200
205
191
197
203
210
194
201
207
214
237
246
255
263
190
197
203
210
82°
85°
90°
95°
83
84
85
87
83
84
85
87
83
84
87
89
84
85
86
87
82
83
84
85
82
83
84
85
190
199
213
228
193
202
216
230
197
206
221
236
206
215
230
245
219
229
245
261
220
229
245
261
TABLE 6
SUCTION SUPERHEAT
82_F OD − 80_F IDDB
/ 67_F IDWB
18 20
18 − 20_
40°
45°
50°
55°
55
62
69
74
51
56
63
70
51
56
63
70
51
55
62
68
51
55
62
68
50
54
61
67
256
265
275
284
211
216
221
227
216
222
229
235
221
227
234
241
272
281
289
298
217
223
230
237
100°
105°
110°
115°
89
90
92
93
89
90
92
93
91
94
96
98
88
89
90
92
86
87
88
90
86
87
88
90
243
257
272
286
244
258
273
287
251
266
281
296
260
275
290
305
277
293
309
326
277
293
308
324
60°
81
78
78
76
76
75
293
232
241
247
307
243
125°
96
96
103
94
92
92
316
315
326
335
358
356