Table 2 Inverter Mode Specifications
INVERTER MODEL
Rated Output Power
Output Voltage Waveform
Output Voltage Regulation
Output Frequency
Peak Efficiency
Overload Protection
Surge Capacity
Nominal DC Input Voltage
Cold Start Voltage
Low DC Warning Voltage
@ load < 50%
@ load ≥ 50%
Low DC Warning Return Voltage
@ load < 50%
@ load ≥ 50%
Low DC Cut-off Voltage
@ load < 50%
@ load ≥ 50%
High DC Recovery Voltage
High DC Cut-off Voltage
No Load Power Consumption
X-4KW-M
4KVA/4KW
Pure Sine Wave
230Vac±10%
50Hz
93%
5s@≥110% load; 10s@105%~110% load
2* rated power for 5 seconds
24Vdc
23.0Vdc
23.0Vdc
22.0Vdc
23.5Vdc
23.0Vdc
21.5Vdc
21.0Vdc
32Vdc
33Vdc
<40W