8 Technical Data

Case
Connectors
Power Supply
Probe Inputs
Valve Output(s)
Serial Connection
Data Storing
Kind of Action
Rated Impulsive Voltage
Operating Temperature
Relative Humidity
Measuring and Regulation Range
Resolution
Document Part # 026-4283 Rev 0
The contents of this publication are presented for informational purposes only and they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein
or their use or applicability. Emerson reserves the right to modify the designs or specifications of such products at any time without notice. Responsibility for proper selection, use and maintenance of any product
4 DIN
Disconnectable terminal block ≤ 2,5 mm2 for valve outputs and minifit
connector for low voltage section
24Vac/dc; Absorption: 40VA max.
2 configurable as NTC/PTC/Pt1000
2 configurable as NTC/PTC/Pt1000/4 to 20mA/ to 5V
See table on page 3
CanBus and LAN for iCHILL200CX
Non volatile memory (EEPROM)
1B; Pollution Grade: 2; Software Class: A
2500V; Over-voltage Category: II
10 to 60 °C; Storage Temperature: -30 to 85 °C
20 to 85% (no condensing)
PTC Probe: -50 to150°C
NTC Probe: -40 to110°C
Pt1000 Probe: -50 to 100°C
Pressure Transducer: -1.0 to 50.0 Bar
0,1°C or 1 °F; Precisione@ 25°C: ±0,1 °C ±1 digit
This document may be photocopied for personal use.
Visit our website at www.climate.emerson.com for the latest technical documentation and updates.
Join Emerson Technical Support on Facebook. http://on.fb.me/WUQRnt
For Technical Support call 833-409-7505 or email ColdChain.TechnicalServices@Emerson.com
remains solely with the purchaser and end-user. ©2022 Emerson is a trademark of Emerson Electric Co.
Page 8 of 8

Advertisement

Table of Contents
loading

Table of Contents