SG 1 - USER MANUAL
Space Guard Series
Photoelectric light curtains
Product Data
Electrical Data
SGT (Transmitter)
Supply voltage
Current consumption
Max. output load
Reverse polarity protected
Short circuit protected
Environmental Data
Light immunity @ 5º incidence
Temperature, operation
Sealing class
Approvals
Available Models
Model
Transmitter
SGT 1(H)-xxx-0xx-x1-x-0x-xx
SGR 1-xxx-0xx-x1-x-00-xx
SGR 1-xxx-0xx-x1-x-01-xx
SGR 1-xxx-0xx-x1-x-02-xx
Receiver
SGR 1-xxx-0xx-x1-x-03-xx
SGR 1-xxx-0xx-x1-x-04-xx
SGR 1-xxx-0xx-x1-x-05-xx
Note:
The high power transmitter, model SGT 1H-xxx-0xx-x1-x-0x-xx has a sensing range of 0,5 to 6,5m.
Connection
Wiring Diagrams
Black wire
Model
connected to ( - )
SGT 1(H)-xxx-0xx-x1-x-00-xx TX is not transmitting
SGT 1(H)-xxx-0xx-x1-x-01-xx TX is not transmitting
SGT 1(H)-xxx-0xx-x1-x-02-xx
TX is transmitting
SGT 1(H)-xxx-0xx-x1-x-03-xx
TX is transmitting
Transmitter SGT
Receiver SGR NPN output
Receiver SGR Solid State Relay output
Installation & Adjustments
Output Logic
Detection
Output mode
Present
Dark operated
Light operated
Absent
Dark operated
Light operated
Website: www.telcosensors.com
E-Mail:
info@telcosensors.com
Made in Denmark
SGR (Receiver)
12 – 36 Vdc
100 mA
50 mA
-
200 mA
Yes
-
Yes
> 100.000 lux
-20 to + 65 ºC
"A" & "B" housing IP 54 - "C" housing IP 67
Output
Output Mode
Sensing Range
-
-
Light operated
NPN
0 – 4m.
Dark operated
(slim line)
Light operated
PNP
0 – 3 m.
Dark operated
(leading edge)
Solid
Dark operated
State
Light operated
Relay
Black wire
Black wire
not connected
connected to ( + )
TX is transmitting
TX is transmitting
TX is transmitting
TX is not transmitting
TX is not transmitting
TX is transmitting
TX is transmitting
TX is not transmitting
Receiver SGR PNP output
Output indicator
Output status
(yellow led)
Closed
Open
Open
Closed
!
This device is not to be used for Personnel Protection in Machine
Guarding Safety applications. This device does not include the self-
checking redundant circuitry necessary to allow its use in personnel
machine guarding stand-alone safety applications.
EN
Adjustment
On the SG1 no initial set up or adjustments are required, due the automatic signal-tracking
(AST) feature, that adjusts automatically each individual beam on the system.
1
Mount the transmitter (SGT) and receiver (SGR) facing each other and correctly aligned.
Wire the sensor according to the wiring diagram.
2
Make sure the load does not exceed 200 mA.
3
Check for correct wiring before turning power on. Select time-out function if required.
When the power on indicator (green LEDs) are on, the system is operating.
4
1.- If the Status indicator (red LED) is constant on the SGR cannot see the SGT.
2.- If the Status indicator (red LED) is flashing slowly one or more beams are blocked
(only if time-out is enabled).
In dynamic installations:
- For initial setup, ensure that the doors where the light curtains are installed, are in the
Note:
fully open position.
- In order to prevent vandalism Telco recommends that the detectors are placed at least
5 mm in the door.
Time-out function
On "A1" model (46 mm channel spacing), up to 4 non-adjacent channels can be ignored with
time-out function enabled, when obstructed for more than 10 seconds.
On "B1" model (92 mm channel spacing), up to 2 non-adjacent channels can be ignored with
time-out function enabled, when obstructed for more than 10 seconds.
This function can be enabled (White wire disconnected) or disabled (White wire connected).
Test Input
The transmitter can be externally disabled and enabled, via the control wire, for test purposes.
Make sure no object is present in the detection area when transmitter is disabled for test.
When the transmitter is disabled, the receiver will change output.
Indicators
SGT
Troubleshooting
Probable Reason
1. Symptom: Output changes when doors are closing.
Misaligned detectors.
The doors are vibrating when closing.
2. Symptom: Status indicator (Red LED) is constant on.
TX is not emitting.
SGT is disabled.
The upper channel is blocked.
2a. For "A1" models (46 mm channel spacing).
More than 4 channels blocked.
2b. For "B1" models (92 mm channel spacing).
More than 2 channels are blocked.
3. Symptom: Status indicator (Red LED) is flashing but correct function of light curtain.
3a. On "A1" model (46 mm channel
spacing), up to four non-adjacent channels
have been blocked or damaged
(time-out function activated).
3b. On "B1" model (92 mm channel
spacing), up to two non-adjacent channels
have been blocked or damaged
(time-out function activated).
On
4. Symptom: Status indicator (Red LED) is flashing and output is not working.
Two adjacent channels are blocked.
Lower channel blocked
Off
5. Symptom: Output indicator (Yellow LED) is flashing
Severe electrical interference.
Off
Severe ambient light.
Cross talk from another light curtain.
On
Warning
tel
SGR
Red LED: Status indicator
Yellow LED: Output indicator
Green LED: Power on indicator
Corrective Action
Align detectors.
Place the detectors further apart from each other.
Check supply and cable to the SGT.
Enable the SGT.
Remove obstruction.
Remove obstruction.
Remove obstruction.
Remove obstruction or prepare to replace the
faulty detector.
Remove obstruction or prepare to replace the
faulty detector.
Remove obstruction or replace detectors.
Remove SGR and SGT supply cable from high
voltage cables.
Change position of SGT and SGR.
Change position of SGT and SGR.
V 1.3 Part Number: 0666220647
Telco A/S reserves the right to make changes without prior notice