Download Print this page

Technical Data; Connection Diagram; Mounting Instruction - Vector MZ3-FU-V01 Manual

3-level switch

Advertisement

Technical Data

Power supply
Signal output
Environment
Standards
General
Product testing and certification
Declaration of
Conformity

Connection diagram

Description:
1 GND
Power supply:
2
V+
Power supply:
3
Not used, do not connect
4
AO
Analog output ventilation: 0/2...10 VDC

Mounting instruction

For more information on mounting, refer to MZ3-FU-V01 Installation Manual No. 70-000841
(www.vectorcontrols.com).
Doc: 70-00-0842A V2.5, 20230220
Subject to alternation
Operating voltage
Power consumption
Electrical connection
Analog output
Output signal
Maximum load
Operation
Climatic conditions
Temperature
Humidity
Transport & storage
Climatic conditions
Temperature
Humidity
Mechanical conditions
Degree of protection
Safety class
Housing material:
Dimensions (H x W x D)
including packaging
Weight (incl. packaging)
Information on the conformity of our products can be found on our website
www.vectorcontrols.com
0 V, -24 VDC, internally connected to signal common
24 VAC, +24 VDC
© Vector Controls GmbH, Switzerland
www.vectorcontrols.com
24 V AC/DC ± 10%, 50/60 Hz, Class 2 48 VA max.
Max. 1 VA
Terminal connectors,
wire 0,34-2,5 mm2 (AWG 22...13)
DC 0...10 V
2 mA or 5 kΩ
To IEC 721-3-3
class 3K5
0...50 ° C (32...122 ° F)
< 95% RH non-condensing
To IEC 721-3-2 and IEC 721-3-1
class 3K3 and class 1K3
-25...70 °C (-13...158 °F)
< 95% RH non-condensing
class 2MT2
Wall mounted:
Not installed:
III (IEC 60536)
Flame retardant PC+ABS plastic (UL94 class V-0)
145 x 105 x 70 mm (5,7" x 4,1" x 2,8")
155 g (5.5 oz)
on the corresponding product page under "Downloads".
MZ3-FU-V01
IP40 acc. EN 60529
IP00 acc. EN 60529
Page 2-6

Advertisement