PRECAUTIONS
• DO NOT RUN THE WIRING IN ANY CONDUIT
WITH LINE VOLTAGE (24/120/230 VAC).
• THE ACI/LCD MUST BE POWERED WITH
EITHER A 24 VAC OR 9-35 VDC POWER
SOURCE.
GENERAL INFORMATION
The S/10K-S series temperature sensors are a system
speci c, plug n' play type sensor that can be ordered
with a 10K Thermistor, Setpoint, "After Hours"
Override (Bypass), and (2) 6 Pin RJ11 Phone Jacks.
The sensor must be connected to the BAS (Building
Automation System) using a 6 Conductor cable
with (2) 6 Pin RJ11 Male phone connectors.
MOUNTING INSTRUCTIONS
For optimal temperature measurement, follow
these tips:
• Do not install on external walls.
• Avoid air registers, di users, vents, and windows.
• Avoid con ned areas such as shelves, closed cabinets, closets, and behind curtains.
• Eliminate and seal all wall and conduit penetrations. Air migration from wall cavities may alter temperature
readings.
• A thermally-insulated backing should be used when tting to solid walls (concrete, steel, etc.). ACI part:
A/ROOM-FOAM-PAD
• Do not install near heat sources, eg: lamps, radiators, direct sunlight, copiers, chimney walls, walls concealing
hot-water pipes.
Take care when mounting. Check local code for mounting height requirements. Typical mounting heights
are 48-60" (1.2-1.5 m) o the ground and at least 1.5' (0.5 m) from the adjacent wall. The sensor should be
mounted in an area where air circulation is well mixed and not blocked by obstructions. Separate the cover
from the base.
ADDITIONAL MOUNTING INSTRUCTIONS FOR OPTIONAL ACI/LCD
The ACI/LCD is shipped as a two-piece unit. The LCD Module must be unplugged from the 10 pin
connector before the base of the sensor may be mounted to either the drywall or over a standard 2" x 4"
Junction Box using the mounting hardware provided. The LCD Module should then be gently inserted into
the 10 pin connector. The cover may now be placed onto the unit and tightened down using the (2) Allen
screws at the bottom of the housing.
Refer to the Wiring Instructions (p. 2) to make necessary connections. After wiring, attach the cover to
the base by snapping the top of the cover on rst and then the bottom. Tighten the cover down, using the
(2) 1/16" Allen screws located in the bottom of the housing. A 1/16" Hex driver is needed to secure the cover
to the base.
Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562
Phone: 1-888-967-5224 | Website: workaci.com
FIGURE 1: ROOM DIMENSIONS
ROOM, VERSION 1
[R]
2.75"
(69.85 mm)
FRONT
BOTTOM
Page 1
Phone: 1-888-967-5224
Website: workaci.com
1.12"
(28.55 mm)
4.50"
(114.30 mm)
RIGHT
Version: 4.0
I0000124

Advertisement

loading

Summary of Contents for aci ROOM Series

  • Page 1 ADDITIONAL MOUNTING INSTRUCTIONS FOR OPTIONAL ACI/LCD The ACI/LCD is shipped as a two-piece unit. The LCD Module must be unplugged from the 10 pin connector before the base of the sensor may be mounted to either the drywall or over a standard 2” x 4”...
  • Page 2 COVER the cover on rst and then the bottom. Note: ACI’s stats are not two-way communicating. Communication jacks allow the user to query and modify operating parameters of the local room terminal FIGURE 3: S/10K-S-RSOFRJ6-LCD unit from the portable operator’s terminal (laptop).
  • Page 3 Display not working WARRANTY The ACI Room Series temperature sensors are covered by ACI’s Five (5) Year Limited Warranty, which is located in the front of ACI’S SENSORS & TRANSMITTERS CATALOG or can be found on ACI’s website: www.workaci.com. W.E.E.E. DIRECTIV At the end of their useful life the packaging and product should be disposed of via a suitable recycling centre.
  • Page 4 Automation Components, Inc. 2305 Pleasant View Road Middleton, WI 53562 Phone: 1-888-967-5224 Website: workaci.com Page 4 Automation Components, Inc. Version: 4.0 2305 Pleasant View Road | Middleton, WI 53562 I0000124 Phone: 1-888-967-5224 | Website: workaci.com...

This manual is also suitable for:

S/10k-s-rsofrj6-lcd