Example Of Radar Installation In Big Room - Jorjin MM5D91-00 Installation Manual

Presence detection sensor
Hide thumbs Also See for MM5D91-00:
Table of Contents

Advertisement

MM5D91-00-InstallationGuide-D01
The radar is mounted on the wall at 2.6m height with 45-degree elevation angle. A 0.2~0.5m
gap between curtain and coverage area is to prevent false alarm caused by curtain.
Figure 2-6. Radar setup in small room (Side view)

2.2.1. Example of radar installation in big room

Figure 2-7. shows a big meeting room of 7.2m x 4.5m, and height 2.8m. As the length of room
is exceeding maximum cover distance (5m), 3 radars are used to cover the room. The radars
are installed at opposite side of the curtain to avoid the disturbance from curtain movement.
Maximum setting of the 3 radars are set to 4m.
Figure 2-7. Radar setup in big room (Top view)
©