The D1xL1 & D1xL2 Loudspeakers are certified
by UL as Audible-signal Appliances for Use in
Hazardous Locations
1)
Introduction
The D1xL1 & D1xL2 are UL certified loudspeakers which
produce a loud warning signal in a hazardous area. The
loudspeaker are approved for use in Gas applications in Class I
Division 1 & 2 as well as Class I Zone 0, 1 and 2.
D1xS1 & D1xS2 alarm horns and D1xC1 & D1xC2 Combined
alarm horn & Strobe are also available as well as variants for
Explosive Dust Atmospheres.
2)
Warnings
CAUTION
TO REDUCE THE RISK OF IGNITION OF HAZARDOUS
ATMOSPHERES:
DISCONNECT FROM SUPPLY BEFORE OPENING.
KEEP TIGHTLY CLOSED WHEN IN OPERATION.
WARNING
FIT SEALING FITTING IN CONDUIT RUNS WITHIN 18
INCHES FROM ENCLOSURE.
EQUIPMENT MUST NOT BE INSTALLED WITH THE HORN
FACING UPWARDS OF HORIZONTAL
ATTENTION
POUR REDUIRE LE RISQUE D'INFLAMMATION DES
ATMOSPHÈRES DANGEREUSES:
COUPER L 'ALIMENTATION AVANT OUVERTURE.
CONSERVER FERMÉ PENDANT LE FONCIONNEMENT.
AVERTISSEMENT
CONDUITS DOIVENT ÊTRE SCELLÉS EN MOINS DE 18
POUCES.
ÉQUIPEMENT NE DOIT PAS ÊTRE INSTALLÉ AVEC LE
KLAXON TOURNÉE VERS LE HAUT DE HORIZONTAL.
__________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH
Document No. D190-00-201-IS-SC
INSTRUCTION & SERVICE MANUAL
D1xL1 & D1xL2 LOUDSPEAKER
For Use In Hazardous Locations - Gas
Issue: 4
27-08-15
3)
Ratings and Markings
3.1 Class / Division Ratings for US and Canada
The D1x Loudspeakers comply with the following standards for
hazardous locations:
UL 1203
CSA C22.2 NO. 30-M1986
The D1xL1 & D1xL2 Loudspeakers also comply with the
following standards for signaling equipment:
UL1480
CSA C22.2 NO. 205-12
3.1 Class / Division Ratings for US & Canada
Class I Div 1
ABCD
Installation must be carried out in compliance with the National
Electric Code / Canadian Electric Code
3.2 Class / Zone ratings US and Canada
Class I Zone 1
IIC T6
Installation must be carried out in compliance with the National
Electric Code / Canadian Electric Code.
3.3 Ambient Temperature Range:
-40ºC to +70ºC
3.4 Enclosure Ratings
The product is rated for ingress protection as follows:
IP rating per EN60529:
Type rating per UL50E / NEMA250: 4 / 4X / 3R / 13
3.5 Electrical Ratings
Model No.
Input
D1xL1-V070
70V Line
D1xL1-R008
8 Ohm
D1xL1-R016
16 Ohm
D1xL2-V070
70V Line
D1xL2-R008
8 Ohm
D1xL2-R016
16 Ohm
3.6 Frequency Range
All models: 400Hz to 8000 Hz
4)
Installation
4.1 Safe Installation Requirements
The product must only be installed by suitably qualified
personnel in accordance with the latest issues of the relevant
standards.
The installation of the units must also be in accordance with the
NEC / CEC and any local regulations and should only be carried
sales@e-2-s.com
www.e-2-s.com
Sheet 1 of 3
T6
Ta -40°C to +70°C
Ta -40ºC to +70°C
IP66
Power
Max I/P
(Watts)
Volts
15
70
15
10.95
15
15.49
25
70
25
14.14
25
20
Tel: +44 (0)208 743 8880
Fax: +44 (0)208 740 4200

Advertisement

loading

Summary of Contents for E2S D1xL1 Series

  • Page 1 INSTRUCTION & SERVICE MANUAL D1xL1 & D1xL2 LOUDSPEAKER For Use In Hazardous Locations - Gas Ratings and Markings 3.1 Class / Division Ratings for US and Canada The D1x Loudspeakers comply with the following standards for hazardous locations: UL 1203 CSA C22.2 NO.
  • Page 2 of unit. Additional entries which are not used must always out by a competent electrical engineer who has the necessary be fitted with suitably certified blanking elements training. The Equipment must not be installed with the horn facing d. Replace the explosionproof cover of the loudspeaker, upwards of horizontal.
  • Page 3 terminals B, C, D or E should be selected depending on what units have blocking capacitors fitted. It should be noted that each output level is required (see table below). loudspeaker has a 1M ohm bleed resistor connected across the blocking capacitor and this should be taken into account when selecting the value of the end of line monitoring resistance.