916SA: Installation, Start-up, Operating and Service and Maintenance Instructions
4. If equipped with permanent, washable filter, clean filter by spraying
cold tap water through filter in opposite direction of airflow. Rinse
filter and let dry. Oiling or coating of the filter is not recommended.
5. If equipped with factory specified disposable media filter, replace
only with a factory specified media filter of the same size.
6. Slide filter into cabinet.
7. Replace filter cabinet door.
8. Turn on electrical supply to furnace.
Blower Motor and Wheel Maintenance
WARNING
!
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury or death.
Blower door switch opens 115-V power to control. No component
operation can occur unless switch is closed. Caution must be taken
when manually closing this switch for service purposes.
To ensure long life, economy, and high efficiency, clean accumulated
dirt and grease from blower wheel and motor annually.
The inducer and blower motors are pre-lubricated and require no
additional lubrication. These motors can be identified by the absence of
oil ports on each end of the motor.
The following items should be performed by a qualified service
technician. Clean blower motor and wheel as follows:
1. Turn off electrical supply to furnace.
2. Remove blower door.
3. All factory wires can be left connected, but field thermostat and
accessory wiring may need to be disconnected depending on their
length and routing.
4. If the vent and combustion air pipe passes through the blower
compartment, it will be necessary to remove the pipes from the
blower compartment.
Disconnect the vent and combustion air pipe by:
a. Loosen the clamps or screw on the vent couplings and
combustion air pipe external to the furnace.
b. Separate the pipes from the couplings and move them aside.
c. Loosen the clamps on the vent couplings and combustion air pipe
located on the blower shelf.
d. Separate the pipes from the blower compartment and set aside.
e. Remove the couplings from the pipe adapters and set aside.
f. After servicing the blower, reverse steps a through e, resealing
combustion air pipe per installation instructions.
g. Tighten all clamps 15 lb -in.
See
Fig. 66
for steps 5 through 14.
5. Remove screws securing blower assembly to blower shelf and slide
blower assembly out of furnace. Detach ground wire and
disconnect blower motor harness plugs from blower motor.
NOTE: Blower wheel is fragile. Use care.
6. On 66100M21 size, the top screw securing blower to shelf must be
removed in order to remove the blower. (See
wheel and motor by using a vacuum with soft brush attachment. Be
careful not to disturb balance weights (clips) on blower wheel
vanes. Do not bend wheel or blades as balance will be affected.
7. If greasy residue is present on blower wheel, remove wheel from
the blower housing and wash it with an appropriate degreaser. To
remove wheel:
NOTE: The DIBC composite wheel used in some models should be
cleaned with mild soapy water only. Allow wheel to dry prior to
reassembly.
a. Mark blower wheel location on shaft before disassembly to
ensure proper reassembly.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
NOTE: Mark blower mounting arms and blower housing so each arm is
positioned at the same hole location during reassembly.
8. Reassemble motor and blower wheel by reversing items 7b through
9. Torque motor mounting bolts to 40 +/- 10 lb-in. when reassembling.
NOTE: Ensure that the removable inlet ring is installed before the
motor on furnaces with a DIBC composite blower.
10. Torque blower wheel set screw to 160 +/- 20 lb-in. when
11. Verify that blower wheel is centered in blower housing and set
12. Spin the blower wheel by hand to verify that the wheel does not rub
Fig.
67)Clean blower
13. Reinstall blower assembly in furnace.
14. Reinstall 2 screws securing blower assembly to blower deck.
15. On 66100M21, ensure that the blower wrapper sits on top of the
NOTE: Be sure to attach ground wire and reconnect blower harness
plugs to blower motor.
16. Downflow or horizontal furnaces with vent pipe through furnace
64
b. Loosen setscrew holding blower wheel on motor shaft.
c. Mark blower wheel orientation and cutoff plate location to
ensure proper reassembly.
d. Remove screws securing cutoff plate and remove cutoff plate
from housing.
e. Remove bolts holding motor mounts to blower housing and slide
motor and mounts out of housing.
f. Remove blower wheel from housing.
g. Clean wheel per instructions on degreaser cleaner. Do not get
degreaser in motor.
7f. Ensure wheel is positioned for proper rotation.
reassembling.
screw contacts the flat portion of the motor shaft. Loosen set screw
on blower wheel and reposition if necessary.
Fig. 66 – Blower Assembly on 30040M14 and 36060M14
on the housing.
two tabs on blower sidewalls. (See
to furnace control. Refer to furnace wiring diagram, and connect
thermostat leads if previously disconnected.
only:
a. Install and connect short piece of vent pipe inside furnace to
existing vent.
b. Connect vent connector to vent elbow.
A190094B
Fig.
67) Reconnect blower leads