SUN2000-(50KTL-ZHM3, 50KTL-M3)
User Manual
Parameter
Grid
connecti
on with
limited
power
(kW)
Issue 05 (2023-02-28)
Description
Active power
Specifies the derating value of the SUN2000 active power
output limit for
by percentage. If the Smart Dongle does not detect any
fail-safe
meter data or the communication between the Smart
Dongle and the SUN2000 is disconnected, the Smart
Dongle delivers the derating value of the SUN2000 active
power by percentage.
Communicatio
In the inverter export limitation scenario, if this parameter
n
is set to Enable, the inverter will derate according to the
disconnection
active power derating percentage when the
fail-safe
communication between the inverter and the Smart
Dongle is disconnected for a period longer than
Communication disconnection detection time.
Communicatio
Specifies the fail-safe detection time for the disconnection
n
between the SUN2000 and the Smart Dongle.
disconnection
This parameter is displayed when Communication
detection time
disconnection fail-safe is enabled.
Closed-loop
● If multiple SUN2000s are cascaded, set this parameter
controller
● If there is only one SUN2000, set this parameter to
Limitation
● Total power indicates export limitation of the total
mode
● Single-phase power indicates export limitation of the
Maximum grid
Specifies the maximum active power transmitted from the
feed-in power
grid-tied point to the power grid.
Power
Specifies the shortest interval for a single export limitation
adjustment
adjustment.
period
Maximum
Specifies the time for detecting power meter data. If the
protection time
Dongle does not detect any power meter data within the
preset time, the Dongle delivers the preset value of Active
power output limit for fail-safe for protection.
Power raising
Specifies the step for grid-tied power adjustment.
threshold
Copyright © Huawei Technologies Co., Ltd.
to SDongle/SmartLogger.
Inverter.
power at the grid-tied point. (When a single-phase
meter is connected, only Total power can be selected. If
a three-phase meter is connected in three-phase three-
wire mode, only Total power can be selected.)
power in each phase at the grid-tied point. If a three-
phase meter is connected, Single-phase power can be
selected only when the meter is connected in three-
phase four-wire mode.