SUN2000-(50KTL-ZHM3, 50KTL-M3)
User Manual
Procedure
Step 1 Crimp OT terminals.
● Avoid scratching the core wire when stripping a cable.
● The cavity formed after the conductor crimp strip of the OT terminal is crimped
● Wrap the wire crimping area with heat shrink tubing or PVC insulation tape.
● When using a heat gun, protect devices from being scorched.
Figure 5-2 Crimping an OT terminal
(1) Cable
(4) OT terminal
Step 2 Connect the PE cable.
Issue 05 (2023-02-28)
NO TE
● The PE point at the AC output port is used only as a PE equipotential point, not a
substitute for the PE point on the enclosure.
● It is recommended that silicone sealant or paint be applied around the ground terminal
after the PE cable is connected.
NO TICE
must wrap the core wires completely. The core wires must contact the OT
terminal closely.
The heat shrink tubing is used as an example.
Copyright © Huawei Technologies Co., Ltd.
(2) Core
(5) Crimping tool
5 Electrical Connections
(3) Heat shrink tubing
(6) Heat gun
37