Table 14. Control Single Character Display Alert Codes (Communicating and Non−Communicating)
Alert
Status of Air Handler
Codes
E 105
Equipment is unable to communicate. Indicates numerous message errors. In most cases errors are related to electrical noise.
E 114
No 60 Hertz Power.
E 115
24−Volt Power Low (Range is 18 to 30 volts).
E 120
Usually caused by delay in outdoor unit responding to indoor unit.
E 124
Active Subnet Controller Missing for > 180 seconds. Equipment lost communication with the thermostat.
E 130
Configuration jumper(s) is missing on AHC.
E 131
Non−volatile data corruption.
E 132
Recycle power. If failure re−occurs, replace control. System reset is required to recover.
E 180
Outdoor air temperature sensor (OAS) out of range.
E 201
Indoor blower communication failure including power outage.
Incorrect air handler model size and capacity selected. Check for proper Configuring under Configuring Unit Size Codes in this
E 202
service manual
E 203
No air handler model size and capacity selected. Check for proper configuration.
E 292
Indoor blower motor unable to start (seized bearing, stuck wheel, etc).
E 295
Indoor blower motor over temperature (motor trip on internal protector).
E 310
Discharge air temperature sensor (DATS) out of range. Code is activated during Field Test Mode.
E 312
Restricted airflow
Indoor blower motor is running at a reduced CFM (cutback mode **).
E 313
Indoor and outdoor unit capacity mismatch (warning only).
Global network connection error. This usually indicates there is a short or overladed resistance is to low) condition between
E 331
communicating indoor and thermostat units.
E 345
Second−stage cooling link not cut. AHC Y1−Y2 link not cut for non−communicating heat pump
E 346
Heat pump link not cut. AHC R−O link not cut for non− communicating heat pump. Only on AHC Rev 2.4 or earlier.
E 347
Relay Y1 failure. AHC relay activated, but not respond back to AHC.
E 348
Relay Y2 failure. AHC relay activated, but not respond back to AHC.
Heat call with no configured or mis−configured electric heat. Check for proper Configuring under Configuring Electric Heat Sections
E 350
in this service manual.
E 351
Heat section / Stage 1 failed
E 352
Heat section / Stage 2 failed (Same as E 351)
E 353
Heat section / Stage 3 failed (Same as E 351)
E 354
Heat section / Stage 4 failed (Same as E 351)
E 355
Heat section / Stage 5 failed (Same as E 351)
E 401
Compressor ran more than 18 hours in air conditioning mode.
E 402
Compressor system pressure trip.
E 403
Compressor short−cycling − running less than four minutes.
E 404
Compressor rotor locked.
E 405
Compressor open circuit.
E 406
Compressor open start circuit.
E 407
Compressor open run circuit.
E 408
Compressor contactor is welded.
E 409
Secondary low voltage. 24VAC is below 18VAC.
®
E 420
When in icomfort
mode with non−communicating HP, defrost cycle running greater than 20 minutes in duration.
** Cutback Mode – The variable speed motor has pre−set speed and torque limiters to protect the motor from damage caused by operating out
of its designed parameters (0 through 0.80 in. w.g. total external static pressure).
pilot relay contacts did not close, or the relay coil in electric heat did not energize.