Installing The Serial Board; Manager3000+ - Setting The Serial Line Parameters; Setting Up The Supervisor Network - Mitsubishi Electric MEHITS MANAGER 3000+ Interface Manual

Table of Contents

Advertisement

IM_MANAGER3000+_TC02_REV00_04_21_EN
4.2

Installing the serial board

Follow the points in paragraph 1 "Installing the serial board" to insert the MODBUS serial board into the controller.
4.3

Manager3000+ - setting the serial line parameters

The communication with the BMS requires the setting of dedicated parameters through the Web interface or the touchscreen
(access the menu using the
key and select the "Device Configuration" page) as described below:
Figure 4.4: "Device configuration" screen
In the SUPERVISOR SETTINGS section set:
PROTOCOL
4.4

Setting up the supervisor network

M-NET Transmission Cable and Modbus cable wiring*
Serial Interface board Included
INFORMATION:
*
Refer to MEHITS Adapter manual for details about connection
The serial cable must be kept separate from the power cables.
The shield of the connection cable must be earthed in just one point
MEHITS S.p.A. ● INTERFACE MANUAL
Modbus Over IP/ Modbus RTU/ BACnet MSTP/BACnet
.
Version 02 - Translation of the original instructions
25