AES SOLAR Subscriber
For power source details, see
Use the Solar Panel selection from the Power From dropdown. .
Note: Can only select Solar Option
When using this selection, 16.5 V AC is the primary power source and the battery is the
Important!
secondary power source.
AC Report Delay: AC Report Delay is active when Suppress AC Fault is set to NO. The report delay is the
time that must pass before the Model 3100S Subscriber will send an AC failure or AC restoral message. This
feature helps prevent mesh network congestion in an area where many Subscribers have an AC power outage
at the same time. Messages can be set to transmit in a staggered fashion using the Random time setting.
The combined AC fail detection time delay of 100 minutes plus the random AC Report Delay between 0‒60
minutes results in time that does not exceed 160 minutes.
AC power must be lost for 100 minutes in order to be detected as a failure. AC power must be restored for at
least 100 minutes in order to be detected as a restore. Once either is detected, a message is created by the
subscriber and is sent to the central station.
An AC report delay is selected based on both this parameter and the setting of AC fault report suppression in the
setting of Suppress AC Fault Reporting.
AC Report Delay – Available settings:
Random Delay: A random time ranging from 0‒60 minutes after 100 minutes of AC power loss.
Enter R into the box.
Fixed delay: A specific time ranging from 1‒60 minutes after 100 minutes of AC power loss.
No Delay: Immediate transmission after 100 minutes of AC power loss. This is not recommended.
Locally Announce AC Fault: Set Locally Announce AC Fault to Yes/No by clicking the Locally Announce AC
Fault switch.
Suppress AC Fault Reporting: Set AC Fault Reporting to Yes/No by clicking the AC Fault Reporting switch.
Suppress Battery Fault Reporting: Set Battery Fault Reporting to Yes/No by clicking the Battery Fault
Reporting switch.
Suppress Charger Fault Report: Set Suppress Charger Fault Report to Yes/No by clicking the Suppress
Charger Fault Report switch.
When changes are complete, click Save Changes.
Power from 24 V DC and Battery
Wiring
Refer to the
section for supply and connection requirements.
Figure
4.
25
AES P/N 40-3100S Rev. 3, 3/14/2023