G1G144-AF49-01
4.2.2 Reactive currents
Because of the EMC filter integrated for compliance with EMC
limits (interference emission and immunity to interference),
reactive currents can be measured in the supply line even
when the motor is at a standstill and the line voltage is switched
on.
The values are typically in the range < 50 mA
At the same time, the effective power in this operating state
(operational readiness) is typically < 2 W.
4.2.3 Residual current circuit breaker (RCCB)
If the use of a residual current device (RCD) is required in your
installation, only pulse-current sensitive and/or AC/DC-
sensitive residual current devices (type F or B) are
permissible. As with variable frequency drives, residual current
devices cannot provide personal safety while the device is
being operated. When the device power supply is switched on,
pulsed charging currents from the capacitors in the integrated
EMC filter can lead to the residual current devices tripping
instantly. We recommend the use of residual current circuit
breakers (RCCB) with a trip threshold of 300 mA and delayed
tripping (super-resistant, characteristic K).
4.2.4 Locked-rotor protection
Due to the locked-rotor protection, the starting current (LRA) is
equal to or less than the nominal current (FLA).

4.3 Plug connection

4.3.1 Making supply connections
CAUTION
Voltage
The device is a built-in component and has no disconnecting
switch.
→ Connect the device to a suitable tripping unit.
→ Only connect the device to circuits that can be switched
off with an all-pole disconnection switch.
→ When working on the device, secure the system/
machine in which the device is installed so as to prevent it
from being switched back on.
; Check your connector's pin assignment.
; Connect the built-in connector with the mating connector.
; Ensure that the connector is properly engaged.