Download Print this page

M-system R7C-EC8B/UL Instruction Manual page 6

Pnp transistor output extension module, 8 points (cc-link v.1.10)

Advertisement

• Points of cautions applicable when wiring the R7C Series
To external apparatus
Keep the cable as
short as possible.
Motor
Drive Cable
SEN TRONIC
Shielded
Cable
Earth
Clamp
Remove a part of the shielded
cable cover and ground it
to the internal panel
plate using an earth
clamp.
To external apparatus
Maintain distance between
cables and noise sources.
056 222 38 18
AG
Keep the wires away from
each other at both ends of
the filter.
To connect with
apparatuses outside
the control panel via
CC-Link, ground the
cable shield using
an earth clamp.
Grounding in pig tail form
is not effective.
mailbox@sentronic.com
www.sentronic.com
R7C-EC8B
Noise
Filter
EM-7801-P Rev.2 P. 6 / 6

Advertisement

loading

This manual is also suitable for:

R7c-ec8b