3 Functions and features

The unit monitors the system temperature in machinery and plants�

4 Function

• The unit displays the current system temperature�
• It features an IO-Link interface and is designed for full bidirectional communi-
cation�
• The unit generates 2 output signals according to the parameter setting:
OUT1/IO-Link:
- Switching signal, limit values for temperature
OUT2: 2 selection options
- Switching signal, limit values for temperature
- Analogue signal for temperature
4.1 Switching function
OUTx changes its switching status if it is above or below the set switching limits�
Hysteresis or window function can be selected�
Hysteresis function
SP
x
rP
x
T = Temperature
SPx = set point
rPx = reset point
HY = hysteresis
Hno = hysteresis NO (normally open)
Hnc = hysteresis NC (normally closed)
4
Window function
FH
x
FLx
T = Temperature
FHx = upper limit value
FLx = lower limit value
FE = window
Fno = window NO (normally open)
Fnc = window NC (normally closed)