American Standard 4A7A4018N Installation And Operation Manual page 4

Condensing units
Table of Contents

Advertisement

2.2 Refrigerant Piping Limits
1. The maximum length of refrigerant lines
from outdoor to indoor unit should NOT
exceed sixty (60) feet.
2. The maximum vertical change should not
exceed sixty (60) feet.
3. Service valve connection diameters are
shown in Table 5.1.
Note: For line lengths greater than sixty (60)
feet, Refer to Refrigerant Piping Application
Guide, SS-APG006-EN or Refrigerant Piping
Software Program, 32-3312-03 (or latest revi-
sion).
2.3 Suggested Locations for Best Reliability
Ensure the top discharge area is unrestricted for
at least five (5) feet above the unit.
Three (3) feet clearance must be provided in
front of the control box (access panels) and any
other side requiring service.
Do not locate close to bedrooms as operational
sounds may be objectionable.
4
Standard
Line Set
150' Max
TOTAL Line Length
Avoid Install
Near Bedrooms
Min. 12" to
Shrubbery
Min 5' Unrestricted
Min 3'
Unrestricted
Access Panel
11-AC11D1-9E-EN

Advertisement