American Standard 4A7A4018N Installation And Operation Manual page 22

Condensing units
Table of Contents

Advertisement

50
51
52
55
7
9
10
60
5
7
8
65
4
70
75
Outdoor
80
Dry
Bulb
85
Temp.
(F)
90
95
100
105
110
115
Using a digital psychrometer, measure the return air wet-bulb temperature at the unit just before the coil. Also measure the outdoor dry-bulb tem-
perature. Use these temperatures to locate the target superheat on the charging table. Do not attempt to charge the system if these conditions fall
outside of this charging table.
ADD refrigerant to DECREASE total superheat. REMOVE refrigerant to INCREASE total superheat. Always allow 10 to 15 minutes of operature
after any refrigerant or air flow change prior to determining the final superheat.
STEP 9 - Record System Information for refer-
ence.
Record system pressures and temperatures
after charging is complete.
Outdoor model number = _________________
Measured Outdoor Ambient = __________ º F
Measured Indoor Ambient = __________ º F
Measured Liquid Line Temp = __________ º F
22
Fixed Orifice Superheat Charging Table
53
54
55
56
57
58
59
11
12
14
15
17
18
20
9
10
12
13
15
16
18
6
8
10
11
13
14
16
5
7
8
10
11
13
5
6
7
9
4
6
Indoor Wet Bulb Temp (F)
60
61
62
63
64
65
66
21
23
24
26
27
29
30
19
21
22
24
25
27
28
17
18
19
21
22
24
25
14
16
17
18
19
21
22
10
12
14
16
18
19
21
7
9
10
11
12
14
16
4
6
7
9
10
13
14
4
6
8
10
11
4
6
8
6
4
Measured Suction Line Temp = __________ º F
Liquid Gage Pressure = __________ PSI
Suction Gage Pressure = __________ PSI
67
68
69
70
71
72
73
30
31
27
28
27
31
24
25
27
28
30
31
22
24
26
28
29
31
32
18
19
21
23
25
26
28
16
18
20
21
23
24
26
13
14
16
18
20
22
24
10
13
14
16
18
20
22
8
10
12
13
16
18
20
6
7
9
11
13
15
18
4
7
9
11
13
16
6
9
12
14
11-AC11D1-9E-EN
74
75
76
77
78
29
31
33
28
29
30
31
32
25
27
28
30
31
23
25
26
28
29
21
23
25
27
29
20
22
24
26
28
18
21
23
26
28
16
19
21
24
26