given supervision or instruction concerning use of the appliance in a safe way and understand
the hazards involved. Children shall not play with the appliance.
Storage
The product must be stored in a dark, dry, frost free and well ventilated place out of the reach
of children. Storage temperatures should be between 0-30
be used for long term storage.
Transport
Prior to transporting the product, it should be removed and stowed safely so as to not incur
damage. The original packaging should be used wherever possible and the product should be
protected from any significant temperatures or vibration.
Installation
Unit Positioning and Accessibility
Caution – Some parts of this product can become very hot and cause
burns. Particular attention has to be given where children and vulnerable
people are present.
The units are intended to be installed more than 1.8m above the floor level, above a
suspended ceiling or at high level where there is no ceiling, exposed to view.
The product is only for indoor use where dry conditions can be guaranteed, in an ambient
temperature range of 10°C – 40°C.
Qualified and professional personnel should be used in all instances to determine exact
methods of working using these instructions as a guide to good practice.
It is the installer's responsibility to ensure that the operational and
environmental limitations of the equipment meet with the project
requirements.
The installer should choose a suitable place to install the unit, noting clearance requirements
for servicing and maintenance as detailed below:
Fans – An access panel is located on the bottom of the unit. This is the full width of the unit.
Minimum 235mm (PROAIR235) or 270mm (PROAIR270) beneath the units and clear access.
Inlet Air Filter – Access to the inlet air filter is from the bottom and out the back inlet of the
unit. Minimum 235mm (PROAIR235) or 270mm (PROAIR270) under the unit with clear access
plus minimum 200mm at rear inlet of unit.
o
C. The original packaging should