Stand-alone reactor dedicated to multifunction regeneration converter

Advertisement

 Cable size, crimp terminal size
Magnetic
MCCB
contactor (MC)
Power
To inverter
supply
MCCB
Dedicated reactor
(FR-XCG)
R/L1
R2/L12
S/L2
S2/L22
T/L3
T2/L32
◆200 V
Crimp terminal
Cable size
Model
Rating
R, S, T
AWG/MCM
R2, S2, T2
8-5
50°C
FR-XCG-7.5K
8
40°C
5.5-5
50°C
FR-XCG-11K
14-5
6
40°C
50°C
FR-XCG-15K
22-6
4
40°C
50°C
FR-XCG-22K
38-6
2
40°C
50°C
1
FR-XCG-30K
60-6
1/0
40°C
50°C
FR-XCG-37K
80-10
2/0
40°C
50°C
FR-XCG-55K
100-10
4/0
40°C
Multifunction
regeneration
converter
P/+
N/-
◆400 V
Crimp terminal
Cable size
Model
Rating
R, S, T
AWG/MCM
R2, S2, T2
50°C
FR-XCG-H7.5K
3.5-5
12
40°C
50°C
FR-XCG-H11K
5.5-5
10
40°C
50°C
FR-XCG-H15K
8-5
8
40°C
50°C
FR-XCG-H22K
14-6
6
40°C
50°C
FR-XCG-H30K
22-6
4
40°C
50°C
4
FR-XCG-H37K
38-8
2
40°C
50°C
FR-XCG-H55K
60-8
2
40°C
FR-XCG-H75K
1/0
50°C
60-10
FR-XCG-H90K
40°C
2/0
FR-XCG-H132K
50°C
300
FR-XCG-H160K
40°C
150-12
FR-XCG-H185K
50°C
400
FR-XCG-H220K
40°C
HEAD OFFICE: TOKYO BUILDING 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
2/2
IB-0600855-D(2211)MEE
Printed in Japan
Specifications subject to change without notice.