System Start-up
M. Check high limit function. Set thermostat to higher
than normal setpoint. Allow boiler to run until high
limit is achieved (180° F default). Burners will shut
down. Note - Hydrostat Economy feature may
cause boiler to cycle before reaching high limit.
N. Adjust gas input rate to boiler.
1. Adjust thermostat to highest setting.
Table 7-4: Input Rate
Size of Gas Meter Dial
Seconds
for One
One-Half
Revolution
Cu. Ft.
30
60
32
56
34
53
36
50
40
45
38
47
40
45
42
43
44
41
46
39
48
37
50
36
52
35
54
33
56
32
58
31
60
30
62
29
64
29
66
29
68
28
70
26
72
25
74
24
76
24
78
23
80
22
111828-01 - 1/23
(continued)
One
Two
Five
Cu. Ft.
Cu. Ft.
Cu. Ft.
120
240
600
113
225
563
106
212
529
100
200
500
90
180
450
95
189
474
90
180
450
86
172
430
82
164
410
78
157
391
75
150
375
72
144
360
69
138
346
67
133
333
64
129
321
62
124
310
60
120
300
58
116
290
56
112
281
54
109
273
53
106
265
51
103
257
50
100
250
48
97
243
47
95
237
46
92
231
45
90
225
8HE
Installation, Operating & Service Instructions
2. Check manifold gas pressure. Manifold
pressure is listed on rating label. Adjust
gas valve pressure regulator as necessary
(turn adjustment screw counterclockwise to
decrease manifold pressure, or clockwise to
increase manifold pressure). If pressure can
not be attained, check gas valve inlet pressure.
If less than minimum gas supply pressure
listed on rating label, contact gas supplier for
assistance.
3. Clock gas meter for at least 30 seconds. Use
Table 7-4 to determine gas flow rate in Cubic
Feet per Hour.
4. Determine Input Rate. Multiply gas flow rate by
gas heating value.
!
WARNING
Failure to properly adjust gas input rate
will result in over firing or under firing of
the appliance. Improper and unsafe boiler
operation may result.
5. Compare measured input rate to input rate
stated on rating label.
a. Boiler must not be overfired. Reduce input
rate by decreasing manifold pressure. Do
not reduce more than 0.3 inch w.c. If boiler
is still overfired, contact your Burnham
Commercial distributor or Regional Office
for replacement Gas Orifices.
b. Increase input rate if less than 98% of rating
plate input. Increase manifold gas pressure
no more than 0.3 inch w.c. If measured
input rate is still less than 98% of rated
input, contact your Burnham Commercial or
regional office for larger orifices.
6. Recheck Main Burner Flame. See Section I
7. Return other gas-fired appliances to previous
conditions of use.
O. Clean Heating System
Oil, grease, and other foreign materials which
accumulate in new hot water boilers and a new or
reworked system should be boiled out, and then
thoroughly flushed. A qualified water treatment
chemical specialist should be consulted for
recommendations regarding appropriate chemical
compounds and concentrations which are
compatible with local environmental regulations.
33