11

APPLICABLE CONTROLS

REQUIREMENT
When the air conditioner is used for the first time,
it will take some moments after the power has
been turned on before the remote controller
becomes available for operations: This is normal
and is not indicative of trouble.
• Concerning the automatic addresses
(The automatic addresses are set up by
performing operations on the outdoor interface
circuit board.)
While the automatic addresses are being set
up, no remote controller operations can be
performed.
Setup takes up to 10 minutes (usually about
5 minutes).
• When the power is turned on after automatic
address setup, it takes up to 10 minutes
(usually about 3 minutes) for the outdoor unit to
start operating after the power has been turned
on.
Before the air conditioner was shipped from the
factory, all units are set to [STANDARD]
(factory default).
If necessary, change the indoor unit settings.
The settings are changed by operating the wired
remote controller.
* The settings cannot be changed using only
a wireless remote controller, simple remote
controller or group control remote controller
by itself so install a wired remote controller
separately as well.
Applicable controls setup
(settings at the site)
Remote controller model name:
RBC-ASCU11-E
Basic procedure
Be sure to stop the air conditioner before
making settings.
(Change the setup while the air conditioner is not
working.)
CAUTION
Set only the Code No. shown in the following
table: Do NOT set any other Code No.
If a Code No. not listed is set, it may not be
possible to operate the air conditioner or other
trouble with the product may result.
3,6
4,5
1
1
Push and hold menu button and [
setting button simultaneously for
10 seconds or more.
• After a while, the display flashes as shown
in the figure. "ALL" is displayed as indoor
unit numbers during initial communication
immediately after the power has been turned
on.
Indoor unit No.
2
Each time [
pushed, indoor unit numbers in the group
control change cyclically. Select the indoor
unit to change settings for.
• The fan of the selected indoor unit runs.
The indoor unit can be confirmed for which
to change settings.
3
Push OFF timer button to confirm the
selected indoor unit.
Set data
4
Push the menu button to make Code No.
[
] flash. Change Code No. [
[
] [
] setting button.
‒ 36 ‒
Installation Manual
2,4,5
7
] [
] setting button is
Code No.
] with
]
36-EN