DOWNTURN NOZZLE KIT INSTALLATION FOR
GAS-FIRED UNIT HEATERS
OPTIONS CD2, CD3, CD4, AND CD5 FOR MODELS UBX, UBZ, UDX, UDZ, AND UEZ
Before installing a downturn nozzle, ensure that the unit is installed using four-point suspension
in accordance with the installation manual provided with the unit.
NOTE: Ensure that the unit location provides sufficient clearance for the nozzle option that is
being installed.
• Refer to the installation manual provided with the heater for important safety information.
• Downturn nozzles are designed to direct the discharge air in a more vertical flow. Refer to
descriptions.
Option
CD2
Downturn of from 25- to 65-degrees
CD3
Downturn of from 50- to 90-degrees
Ensure that all components listed in
Table 2. Kit Components—Models UBX, UBZ, UDX, and UDZ
Component
Option
CD2
CD3
Kit package
CD4
CD5
CD2, CD4
Right nozzle
panel
CD3, CD5
CD2, CD4
Left nozzle
panel
CD3, CD5
CD2, CD4
Top nozzle
panel
CD3, CD5
CD2, CD4
Nozzle bottom
CD3, CD5
Nozzle
CD2, CD3,
blockoff
CD4, CD5
Blockoff panel
CD3, CD5
Louver frame
Vertical louver
CD4, CD5
Louver spring
Screw, sheet metal, 8-18 × 3/8
*
Quantity is one (1) unless otherwise indicated. AR = as required.
DO NOT DESTROY. PLEASE READ CAREFULLY. KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.
Revision: UBX-UBZ-UDX-UDZ-UEZ-CD2,3,4,5 (03-23) 1036421-B
Supersedes: UBX-UBZ-UDX-UDZ-UEZ-CD2,3,4,5 (04-22) 1036421-A
⚠ DANGER ⚠
Table 1. Downturn Nozzle Options
Description
KIT COMPONENTS
Table 2
Table 3
or
Model
030, 045
UBX, UDX
1036261
UBZ, UDZ
1036267
UBX, UDX
1036273
UBZ, UDZ
1036279
UBX, UDX
1036285
UBZ, UDZ
1036291
UBX, UDX
1036306
UBZ, UDZ
1036312
1033918
All
1033918 (2)
1033917
All
1033917 (2)
1033919
All
1033919 (2)
1033921
All
1033921 (2)
UBX, UDX
1036215
UBZ, UDZ
1036209
All
1033920
1028413
All
1028418 (5)
195046 (5)
Option
CD4
CD5
are available before beginning installation.
Unit Size
060, 075
100, 125
PN (Quantity)
1036262
1036263
1036268
1036269
1036274
1036275
1036280
1036281
1036286
1036287
1036292
1036293
1036307
1036308
1036313
1036314
1034681
1034682
1034681 (2)
1034682 (2)
1034676
1034677
1034676 (2)
1034677 (2)
1034671
1034672
1034671 (2)
1034672 (2)
1033921
1033921
1033921 (2)
1033921 (2)
1034686
1036205
1036210
1036211
1036216
1036217
1028433
1028443
1028434 (5)
1028441 (5)
195046 (5)
195046 (5)
195638 (AR)
Table 1
Description
CD2 nozzle with vertical louvers (option CD1)
CD3 nozzle with vertical louvers (option CD1)
150, 175, 200
225, 250
*
1036264
1036265
1036270
1036271
1036276
1036277
1036282
1036283
1036288
1036289
1036294
1036295
1036309
1036310
1036315
1036316
1034683
1034684
1034683 (2)
1034684 (2)
1034678
1034679
1034678 (2)
1034679 (2)
1034673
1034674
1034673 (2)
1034674 (2)
1034669
1034669
1034669 (2)
1034669 (2)
1036206
1036207
1036212
1036213
1036218
1036219
1033695
1033715
1033904 (8)
1033961 (8)
195046 (8)
195046 (8)
for option
300, 350, 400
1036266
1036272
1036278
1036284
1036290
1036296
1036311
1036317
1034685
1034685 (2)
1034680
1034680 (2)
1034675
1034675 (2)
1034670
1034670 (2)
1036208
1036214
1036220
1033728
1033730 (8)
195046 (8)

Advertisement

loading
Need help?

Need help?

Do you have a question about the CD2 and is the answer not in the manual?

Questions and answers

Summary of Contents for Reznor CD2

  • Page 1 Supersedes: UBX-UBZ-UDX-UDZ-UEZ-CD2,3,4,5 (04-22) 1036421-A DOWNTURN NOZZLE KIT INSTALLATION FOR GAS-FIRED UNIT HEATERS OPTIONS CD2, CD3, CD4, AND CD5 FOR MODELS UBX, UBZ, UDX, UDZ, AND UEZ ⚠ DANGER ⚠ Before installing a downturn nozzle, ensure that the unit is installed using four-point suspension in accordance with the installation manual provided with the unit.
  • Page 2 1042330 (2) CD2, CD4 1036678 1036684 1036690 1042324 1042329 Nozzle bottom 1036678 (2) 1036684 (2) 1036690 (2) 1042324 (2) 1042329 (2) Nozzle blockoff CD2, CD3, CD4 1036680 1036686 1036692 1042326 1042331 Blockoff panel 1036679 1036685 1036691 1042597 1042598 Louver frame 1036666...
  • Page 3 Figure 2. Typical Face Plate Assembly (with Vertical Louver Frame Shown) NOTE: The vertical louver frame is installed only on units ordered with either option CD4 or CD5— vertical louvers (option CD1) with either a CD2 nozzle or a CD3 nozzle. Figure 2) in face plate outlet so that holes align 5.
  • Page 4 12. Light heater in accordance with lighting instructions. 13. Check for proper operation. Specifications and illustrations subject to change without notice or incurring obligations. Latest version of this manual is available at www.reznorhvac.com. ©2023 Nortek Global HVAC LLC, O’Fallon, MO. All rights reserved. UBX-UBZ-UDX-UDZ-UEZ-CD2,3,4,5 (03-23) 1036421-B...