Warnings FOR YOUR SAFETY What to do if you smell gas: • Do not try to light any appliance. • Do not touch any electrical switch; do not use any phone in your building. • Immediately call your gas supplier. •...
1. General Models UDSA 008-2 through 100-2 are design certifi ed to the CE EN1020 stan- dard for use in industrial and commercial installations only. All models and sizes are available for use with either natural, propane or butane gas. The type of gas, the input rate and the electrical supply requirement is shown on the heater rating plate.
Clearances (mm) Units must be installed so that the minimum clearances in the following table are provided for combustion air space, inspection and service and for proper spacing from combustible materials. Table 2 : Clearances (mm) Model Z (*) 008-2 → 030-2 035-2 →...
Page 7
Table 4b : Technical data TYPES 008-2 → 030-2 Type 008-2 011-2 015-2 020-2 025-2 030-2 Comb. Air & Flue, type B instal. Comb. Air & Flue, type C instal. C12, C32, C42, C52, C62, C82 Flue & combustion air connection collars Heat input (Hs) 13,2 17,6...
7. Flue Model UDSA-2 heaters may be installed as Type-B and Type-C installations. Flue must be in accordance with BS6230 or BS5440. Local requirements may ap- requirements ply in addition to national requirements. These unit heaters are designed to operate safely and effi...
Page 9
Venter outlet attachment requirements: Flue outlet Depending on the size of fl ue pipe as determined in table 5, attach either the fl ue pipe directly to the collar or a taper-type connector. WARNING : Single wall fl ue pipe exposed to cold air or run through unheated areas should be insulated to avoid condensation.
Page 10
Figure 3 : Type B appliances : Combustion air and fl ue pipe sockets all mod., except. 035-2,043-2, 050-2 only mod. 035-2, 043-2 & 050-2 1) Flue pipe outlet collar 2) Combustion air inlet opening It is important to ensure that there is an adequate air supply at all times for both Air supply combustion and heating requirements.
Page 11
Balanced fl ue air heaters are designed to be fi tted with a combustion air inlet duct Combustion air inlet that obtains outdoor air and a fl ue pipe that exhausts fl ue products to outdoors. pipe & fl ue pipe Both the fl...
8. Location Use the minimum clearances in section 5 and the throw data in the technical data table of section 6 when determining where to suspend the heater. heater Recommended minimum height is 2.5mm. Remark: Flue requirements may affect location. WARNING: If touched, the vent pipe and internal heater surfaces Consult section 7...
9. Hanging Before suspending the heater, check the supporting structure to verify that it has suffi cient load-carrying capacity to support the weight of the unit. the heater WARNING: Leave the unit on the pallet. If the bottom of the unit is not supported or protected damage can occur.
Page 14
When desired the heaters may be supported by wall brackets. Supporting in this Figure 7 : manner allows the heaters to be placed in close proximity to the ceiling or mounted Wall bracket kits (optional) directly to the vertical supporting structures of the building. There are 2 different wall bracket designs for UDSA-2 models as shown in the illustrations below.
10. Gas Piping Warning : This appliance is equipped for a maximum gas supply pressure of 50 mbar. pressures WARNING : Pressure testing supply piping Test pressures above 50mbar : Disconnect the heater and manual valve from the WARNING: All com- gas supply line which is to be tested.
11. Electrical The electrical installation may only be carried out by an appropriately qualifi ed person current to IEE Regulations. The supply line to the heater should include supply and a main switch. The minimum clearance distance between the contacts must be connections more than 3 mm.
Page 17
Figure 9 : Wiring connections on the terminal board 1103UDSA-2--EN, Pag. 17/36...
12. Check Check suspension. Unit must be secure.Verify that no other parts are fi tted which are not individually supported and secured. installation Check clearances from combustibles. Requirements are in section 5. & start-up Check vent system to be sure that it is installed according to the instructions in section 7, venting requirements.
Page 19
1. Set thermostat to the lowest setting. Operating instructions and 2. Turn off all electric power to the heater. operating sequence Shut the gas cock at the inlet of the unit. Wait fi ve (5) minutes to clear out any gas. Then smell for gas, including near the fl...
Page 20
The gas pressure is set for the required heat input before the appliance leaves the Burner gas pressure factory. Provided that the gas supply to the air heater is in accordance with the adjustment supply pressure described on the appliance data plate, the operating pressure will not require adjustment.
Page 21
Figure 10b : HONEYWELL gas valve (type 035-2 -> 100-2) Legend Gas inlet Gas outlet Inlet pressure tap Outlet pressure tap 6.3mm AMP terminals and screws for wiring 6.3mm AMP terminals Earth terminal/screw (line voltage models only) Pressure regulator adjustment screw Table 8 : Burner jets and pressures *Belarus, China, Croatia, Czech Republic, Cyprus, Estonia, Greece, Iceland, Latvia, Lithuania, Montenegro, New Zealand, Portugal,Serbia, Slovenia, Slovakia, Spain, Turkey...
Page 22
Ignition This heater is equipped with a direct spark integrated control relay. The control relay monitors the safety devices and controls the operation of the venter motor system and the gas valve between heat cycles. Normal The time line below illustrates a normal heat cycle. Heat Cycle Operating Sequence...
13. Maintenance The material contained in the MAINTENANCE AND SERVICE Section of this manual is designed to aid a qualifi ed service technician in maintaining and ser- & Service vicing this equipment. This heater will operate with a minimum of maintenance. To ensure long life and satisfactory performance, a heater that is operated under normal conditions should be inspected and cleaned at the start of each heating Warning :...
15. Burner This heater has a unique one-piece burner assembly designed to provide ® -CORE controlled fl ame stability without lifting or fl ashback. The burner can be removed Maintenance as a unit for inspection or service : see below for removal instructions. Inspect the burner/control compartment annually to determine if cleaning is neces- sary.
Page 26
6. Remove burner Figure 13a a) Locate the burner body front support. Remove the screws that attach it to the secondary air shield. Refer to fi g. 14 for component defi nitions. b) Holding the venturi tube, slide the entire burner slightly to the right to disengage the burner from the supports on the left.
Inspect and clean the With the burner assembly removed, shine a fl ashlight on the burner ribbons. Look for carbon buildup, scale, dust, lint, and/or anything that might restrict fl ow through burner the spaces between the burner ribbons. Holding the burner assembly so that any foreign material will fall away from the burner, use a stiff bristle brush to loosen Figure 15 and remove any foreign material(s).
Figure 16a Ignitor showing required spark gap measurement Figure 16b Flame sensor Caution : Due to high Flame sensor - Refer to fi gure 11a and locate the fl ame sensor. Disconnect the wire, remove the screw and the fl ame sensor. Clean with an emery cloth.. voltage on the spark wire and electrode, do not touch Control relay - See fi...
3. Remove the fan assembly (fan guard, motor and fan blade). Figure 18 - Fan blade position on the motor 4. Disassemble and replace parts as needed, then reassemble. shaft Be sure the fan blade is in the proper position on the shaft; refer to the illustra- tion and table in fi...
Page 30
Venter wheel position on UDSA models 008-2 - 020-2 shaft (Rotation clockwise from motor shaft end) Figure 19 Venter motor Motor mounting plate bracket Venter wheel Motor cooling fan 8 mm UDSA models 025-2 - 030-2 (Rotation clockwise from motor shaft end) Figure 20 Venter wheel...
UDSA models 035-2 - 100-2 (Rotation counter clockwise from motor shaft end) Figure 21 Venter motor plate Motor mounting bracket Venter wheel Motor cooling 8 mm 21. Operating The main operating quick opening gas valve is powered through the thermostat and safety controls.
22. Combustion The combustion air pressure switch ensures that proper combustion airfl ow is available. The switch senses the differential pressure between the negative pressure air pressure in the fl ue gas collector box and the pressure in the control section. (For switch switch location, see fi...
24. Flue and Check the complete system at least once a year. Inspection should include all joints, combustion seams, concentric adapters and the fl ue terminal cap. Replace any defective or heavily corroded parts. air piping 25. Trouble- The integrated control relay monitors the operation of the heater. If the heater fails to operate properly, review the fl...
General Troubleshooting PROBLEM PROBABLE CAUSE REMEDY Venter motor 1. No power to unit 1. Turn on power, check supply fuses or circuit breaker. will not start 2. No power to venter motor 2. Check connections at burner relay and/or venter motor terminals. 3.
Need help?
Do you have a question about the UDSA 008-2 and is the answer not in the manual?
Questions and answers