Honeywell SILENT KNIGHT EVS Series Manual page 38

Emergency voice system
Table of Contents

Advertisement

EVS Device Installation
Wiring Lengths
Number Of Speakers
@1/2 W
10
20
30
40
52
80
100
NOTE: The above table assumes a uniform distribution of the speakers, and that a max of 20% voltage drop on the last speaker is allowed
Class B Speaker Configuration for EVS-100W
Figure 4.39 illustrates how to wire speakers to the control panel using Class B supervision.
38
Total Load
@1 W
Vrms
Watts
5
25Vrms
5W
70Vrms
10
25Vrms
10W
70Vrms
15
25Vrms
15W
70Vrms
20
25Vrms
20W
70Vrms
26
25Vrms
26W
70Vrms
40
25Vrms
40W
70Vrms
50
25Vrms
50W
70Vrms
Table 4.5 Wire Lengths
AUDIO CIRCUIT OUT
AUDIO CIRCUIT OUT
AUDIO CIRCUIT IN
supervised,
power-limited
Figure 4.39 Class B Speaker Configuration
Wire Distance in Feet
18 AWG
16 AWG
3900
6200
25000
39700
2125
3380
15200
24150
1460
2320
11000
17500
1100
1750
8500
13510
760
1200
6100
9700
550
875
4100
6500
450
715
3500
5560
AUDIO CIRCUIT IN
EVS Series Manual — P/N LS10062-001SK-E:D 3/15/2022
Installing the EVS-100W
14 AWG
12 AWG
9860
15680
63200
100520
5375
8540
38400
61100
3690
5870
27800
44200
2780
4420
21500
34175
1920
3050
15400
24520
1390
2200
10360
16480
1130
1800
8850
14070
15kΩ EOL