SPLIT-TYPE AIR CONDITIONERS
INSTALLATION MANUAL
1. BEFORE INSTALLATION
1-1. THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY
• Be sure to read these safety precautions and instructions.
• After reading this manual, be sure to store it with the OPERATING INSTRUCTIONS for future reference.
• Please report to your supply authority or obtain their consent before connecting this equipment to the power supply system.
Do not install the unit by yourself (user).
whom you purchased the unit.
Follow the instructions detailed in the installation manual.
ing, or leakage of water.
When installing the unit, use appropriate protective equipment and tools for
safety.
Failure to do so could cause injury.
Install the unit securely in a place that can bear the weight of the unit.
If the installation location cannot bear the weight of the unit, the unit could fall
causing injury.
Perform electrical work according to the installation manual and be sure to use
an exclusive circuit. Do not connect other electrical appliances to the circuit.
Ground the unit correctly.
Do not connect the ground wire to a gas pipe, water pipe, lightning rod or tel-
ephone ground. Defective grounding could cause electric shock.
Do not damage the wires.
wiring.
Failure to do so could cause electric shock.
If gas leaks and accumulates around the unit, it could cause an explosion.
Do not use intermediate connection of the power cord or the extension cord.
Do not connect many devices to one AC outlet.
an electric shock, the unit falling, etc.
When plugging the power supply plug into the outlet, make sure that there is
no dust, blockage, or loose parts both in the outlet and on the plug. Verify that
the power supply plug is completely in the outlet.
If there is dust, blockage, or loose parts on the power supply plug or the outlet, it could
Securely attach the electrical cover to the indoor unit and the service panel to
the outdoor unit.
If the electrical cover of the indoor unit and/or the service panel of the outdoor unit are
an electric shock.
Depending on the installation area, install a Ground Fault Interrupt (GFI) circuit
breaker.
If the Ground Fault Interrupt (GFI) circuit breaker is not installed, an electric shock
could occur.
Perform the drainage/piping work securely according to the installation manual.
If there is defect in the drainage/piping work, water could drip from the unit, and
damage household items.
JG79A805H07
MSZ-FH06/09/12/15/18NA
MSZ-FH18NA2
When installing multi units, refer to the
installation manual of the multi unit for out-
door unit installation.
WARNING
-
-
CAUTION
Required Tools for Installation
Phillips screwdriver
Level
Scale
Utility knife or scissors
3 in. (75 mm) hole saw
Torque wrench
Wrench (or spanner)
(Could lead to death or serious injury.)
When installing, relocating, or servicing the unit, make sure that no substance
Any presence of foreign substance such as air can cause abnormal pressure rise
and may result in explosion or injury. The use of any refrigerant other than that
breakdown. In the worst case, this could lead to a serious impediment to securing
product safety.
Do not discharge the refrigerant into the atmosphere. Check that the refriger-
ant gas does not leak after installation has been completed. If refrigerant leaks
during installation, ventilate the room.
heater, space heater, stove, etc., harmful gases will be generated.
Use appropriate tools and piping materials for installation.
The pressure of R410A is 1.6 times higher than R22. Not using the appropriate
tools and materials, or improper installation could cause the pipes to burst causing
an injury.
When pumping down the refrigerant, stop the compressor before disconnecting
the refrigerant pipes.
If the refrigerant pipes are disconnected while the compressor is running and the
stop valve is open, air could be drawn in and the pressure in the refrigeration cycle
could become abnormally high, causing the pipes to burst.
When installing the unit, securely connect the refrigerant pipes before starting
the compressor.
If the compressor is started before the refrigerant pipes are connected and the
stop valve is open, air could be drawn in and the pressure in the refrigeration cycle
could become abnormally high, causing the pipes to burst.
Install the unit according to national wiring regulations.
Exercise caution when using any auxiliary heat source and follow all third party
manufacturer instructions and safety guidelines for installation and usage.
Any auxiliary heat source connected to this unit via the CN24 connection must
have an independent temperature control mechanism. Failure to install and main-
tain such temperature control mechanism may void the warranty for this unit.
Mitsubishi Electric shall not bear any warranty obligation or other liability for any
damage or loss in connection with such third party auxiliary heaters.
(Could lead to serious injury when operated incorrectly.)
This could cause injury.
Do not install the outdoor unit where small animals may live.
If small animals enter the unit and damage its electrical parts, it could cause a
5/32 in. (4 mm) hexagonal wrench
Flare tool for R410A
Gauge manifold for R410A
Vacuum pump for R410A
Charge hose for R410A
Pipe cutter with reamer

Advertisement

Table of Contents
loading

Summary of Contents for Mitsubishi Electric MSZ-FH06NA

  • Page 1 Mitsubishi Electric shall not bear any warranty obligation or other liability for any When plugging the power supply plug into the outlet, make sure that there is damage or loss in connection with such third party auxiliary heaters.
  • Page 2: Selecting The Installation Location

    1-3. SPECIFICATIONS 1-3-1. POWER SUPPLY AND INDOOR/OUTDOOR WIRE CONNECTION MSZ-FH06NA MSZ-FH15NA • Power should be taken from an exclusive branched circuit. MODEL MSZ-FH09NA MSZ-FH18NA •...
  • Page 3: Installation Diagram

    1-4. INSTALLATION DIAGRAM ACCESSORIES Wall hole cover (D) Use the wall hole sleeve Check the following parts before installation. Indoor unit (C) to prevent indoor/ Seal the wall hole <Indoor unit> outdoor connecting wire gap with putty (H). Installation plate (A) from contacting metal Wall hole parts in the wall and to...
  • Page 4: Indoor Unit Installation

    2. INDOOR UNIT INSTALLATION 2-1. ATTACHING THE INSTALLATION PLATE Ceiling 3-3/8 in. (85 mm) or more 5-11/16 in. (143 mm) or more for left and left back piping (using spacer) • To prevent installation plate (1) from vibrating, be sure to install the attachment screws in Installation plate (1) Level the holes indicated in the illustration.
  • Page 5: Pipe Forming And Drain Piping

    2-4. PIPE FORMING AND DRAIN PIPING 2-4-1. PIPE FORMING • Place the drain hose below the refrigerant piping. Felt tape (4) • Make sure that the drain hose is not crowded or bent. Piping tape (G) • Do not pull the hose when applying the tape. Liquid pipe •...
  • Page 6: Outdoor Unit Installation

    3. OUTDOOR UNIT INSTALLATION 3-1. CONNECTING WIRES FOR OUTDOOR UNIT 1) Remove the service panel. 2) Remove the conduit cover. 3) Attach the conduit connectors to the conduit plate with lock nuts then secure it against unit with screws. 4) Connect the ground wires of indoor/outdoor unit connecting wire (A) and power supply cord (K) 19/32 in.
  • Page 7: Purging Procedures, Leak Test, And Test Run

    3-3. PIPE CONNECTION • Be sure to wrap insulation around the piping. Direct contact with the bare piping may result in burns or frostbite. Indoor unit connection Connect both liquid and gas pipings to indoor unit. frigeration oil on screw threads. Excessive tightening torque will result in damage on the screw.
  • Page 8: Relocation And Maintenance

    5. RELOCATION AND MAINTENANCE 5-1. REMOVING AND INSTALLING THE PANEL ASSEMBLY Removal procedure 1) Unlock the upper and lower vanes as shown in using a thin instrument. Then, remove the horizontal vanes. 2) Remove the front panel. 4) The panel assembly consists of 3 components. Remove them in the following Unlock order: right, left, and center bottom.
  • Page 9: Avant L'installation

    électrique ou un incendie. Remplacez Mitsubishi Electric n’acceptera aucune obligation de garantie ni aucune autre les éventuels éléments desserrés. Fixez correctement le couvercle du boîtier électrique de l’unité interne et le auxiliaires tiers.
  • Page 10 Dans les zones soumises à de fortes chutes de provoquer un craquage chimique. neige, installez un abri, un socle et/ou des écrans de protection. 1-3. FICHE TECHNIQUE 1-3-1. BRANCHEMENT DU CORDON D’ALIMEN- TATION ET DU CABLE DE CONNEXION DE MSZ-FH06NA MSZ-FH15NA L’UNITE INTERNE/EXTERNE MODELE MSZ-FH09NA MSZ-FH18NA MSZ-FH12NA MSZ-FH18NA2 •...
  • Page 11: Schema D'installation

    1-4. SCHEMA D’INSTALLATION ACCESSOIRES Cache d’ouverture murale (D) Utilisez le manchon Unité d’ouverture murale <Unité interne> Bouchez l’ouverture interne (C) pour éviter tout murale avec du mastic (H). Gabarit d’installation contact entre le câble Manchon de connexion de l’unité Fixez le tuyau au mur d’ouverture à...
  • Page 12: Installation De L'unite Interne

    2. INSTALLATION DE L’UNITE INTERNE 2-1. FIXATION DU GABARIT D’INSTALLATION Plafond 3-3/8 in. (85 mm) minimum 5-11/16 in. (143 mm) minimum pour la tuyauterie gauche ou arrière gauche (utiliser une entretoise) Gabarit d’installation (1) Niveau 4-7/8 in. 5-1/4 in. (122,5 mm) (132,5 mm) minimum minimum...
  • Page 13 2-4. MISE EN FORME DE TUYAU ET TUYAU DE VIDANGE 2-4-1. MISE EN FORME DE TUYAU • Placez le tuyau de vidange sous la conduite de réfrigérant. • Assurez-vous que le tuyau de vidange n’est ni encombré ni plié. Bande de feutre (4) Ruban adhésif de tuyauterie (G) •...
  • Page 14 3. INSTALLATION DE L’UNITE EXTERNE 3-1. RACCORDEMENT DES CABLES DE L’UNITE EXTERNE 1) Retirez le panneau de service. 2) Déposez le cache de conduit. plaque sur l’unité avec des vis. 19/32 in. 4) Raccordez les câbles de terre du câble de connexion de l’unité interne/externe (A) et du cor- (15 mm) don d’alimentation (K) au support TB.
  • Page 15 3-3. RACCORDEMENT DES TUYAUX reporter à la section 3-2). • S’il est trop serré, il risque de se rompre et de provoquer une fuite de réfrigérant. • Assurez-vous que la tuyauterie est enveloppée d’isolant. Un contact direct avec la tuyauterie nue peut entraîner des brûlures ou des engelures. Raccordement de l’unité...
  • Page 16: Deplacement Et Entretien

    5. DEPLACEMENT ET ENTRETIEN 5-1. DEPOSE ET INSTALLATION DU PANNEAU Dépose 2) Déposer le panneau frontal. 4) L’ensemble du panneau se compose de 3 composants. Retirez-les dans l’ordre Déver- suivant: droite, gauche, et centre bas. Pour retirer le composant droit, tirer sur le rouiller coin supérieur droit.