TxIsoRail
ISOLATED TRANSMITTER – USER GUIDE − V1.0x
1.
SPECIFICATIONS
Sensor input: User defined. The supported sensors are listed in
Table 1, along with their maximum ranges.
Thermocouples: Types J, K, R, S, T, N, E, and B, according to
IEC 60584 (ITS-90). Impedance >> 1 MΩ
Pt100: 3-wire connection, Excitation: 180 µA, α = 0.00385,
according to IEC 60751 (ITS-90).
For 2-wire Pt100, tie terminals 2 and 3 together.
Voltage: 0 to 50 mVdc, 0 to 10 Vdc. Impedance >> 1 MΩ.
Current: 0 to 20 mA, 4 to 20 mA. Impedance 15.0 Ω (+ 1.9 Vdc).
SENSOR TYPE
RANGE
Thermocouple K
-150 to 1370 °C / -238 to 2498 °F
Thermocouple J
-100 to 760 °C / -148 to 1400 °F
Thermocouple R
-50 to 1760 °C / -58 to 3200 °F
Thermocouple S
-50 to 1760 °C / -58 to 3200 °F
Thermocouple T
-160 to 400 °C / -256 to 752 °F
Thermocouple N
-270 to 1300 °C / -454 to 2372 °F
Thermocouple E
-90 to 720 °C / -130 to 1328 °F
Thermocouple B
500 to 1820 °C / 932 to 3308 °F
Pt100
-200 to 600 °C / -328 to 1112 °F
0 to 50 mV
Voltage
0 to 10 V *
0 to 20 mA
Current
4 to 20 mA
Table 1 – Transmitter input sensors
* Note: 0-10 Vdc input type requires an internal jumper switching.
Response time: < 500 ms
Electrical isolation: 1000 V for 1 minute between input and output.
Maximum load (RL): RL (max.)= (Vdc – 12) / 0.02 [Ω]
Where: Vdc = Power supply voltage
Operating temperature: -40 to 85 °C / -40 to 185 °F
Humidity: 0 to 90 % UR
Electromagnetic compatibility: EN 50081-2, EN 50082-2
Internal protection against polarity inversion.
Cold Junction compensation for thermocouples.
Certifications: CE, UKCA.
1.1
4-20 mA MODEL
Output: 4-20 mA or 20-4 mA current, 2-wire type; linear to input
signal.
Output resolution: 0.001 mA (14 bits)
Total accuracy: 0.30 % of maximum range for thermocouples, ±1
°C;
0.20 % of maximum range for Pt100, voltage, and
current.
Power Supply: 12 to 35 Vdc, voltage applied to the transmitter.
NOVUS AUTOMATION
1.2
Output: Voltage 0 to 10 Vdc or 10 to 0 Vdc; linear to input signal.
Output resolution: 0.0006 V (14 bits)
Total accuracy: 0.25 % of maximum range for thermocouples, ±1
Power supply: 18 to 30 Vdc, voltage applied to the transmitter.
2.
When the transmitter is used with the factory setting, no further
MINIMUM
action is required, and the transmitter is ready to be installed.
MEASUREMENT
SPAN
When it is necessary to change the configuration of the equipment,
you should use SigNow software, TxConfig software, or SigNow
100 °C / 212 °F
app.
100 °C / 212 °F
To configure the equipment through any of the software, you must
400 °C / 752 °F
connect the TxConfig Configuration Interface (purchased from the
manufacturer or its authorized representatives) to the USB port of
400 °C / 752 °F
the computer used and run the selected software, as shown in
100 °C / 212 °F
Figure 1:
100 °C / 212 °F
100 °C / 212 °F
400 °C / 752 °F
40 °C / 104 °F
5 mV
1 V
2 mA
2 mA
To configure the device via SigNow app, you need to use an OTG
cable with the TxConfig Configuration Interface and proceed with
the recognition process (see
chapter).
On NOVUS website, you can download the configuration software
for free. To install it, simply run the file SigNowSetup.exe or the file
TxConfigSetup.exe and follow the instructions in the installer.
The SigNow setup application can be downloaded for free from the
Google Play Store or the App Store.
0-10 VDC MODEL
°C;
0.15 % of maximum range for Pt100, voltage, and
current.
CONFIGURATION
Figure 1 – TxConfig Interface USB connections
1/5