10.4 FINAL INSPECTION

Check that:
• The impeller is mounted for the correct direction of rotation.
• All screws and nuts have been tightened to the corrrect torque values.
• No foreign objects have been left in the casing or in the ducting.
• The mechanical opening of the hatch works.

10.5 MECHANICAL OPENING OF THE DOOR

The mechanical opening of the hatch is intended for emergency situations where the door has to be opened when
the electrical supply has been disrupted/turned off.
The door can be opened mechanically by pulling the wires under the hatch. There are two wires, and they are
located on both sides of the linear motors. Pulling on the wire requires some force, so you must use an aid, such as
a steel rod, formed into a hook (see picture for example).
After mechanically opening the lid, re-attach the linear motor shafts to the mounting lugs and make sure that the
cover seals are intact.

11. FAULTS

If any faults occur during inspection which cannot be repaired by maintenance personnel, please contact the
service department at Woods Air Movement.
Examples of faults can include the following issues:
• Foreign bodies inside the fan
• Corroded items (fixings etc.) which are located inside the casing
• High vibrations
• Maintenance negligent
• Hatch not opening
Possible problems generated:
• Bearing damage
• Corrosion damage
• Excessive vibration generated damage
14

12. SPARE PARTS

Only use genuine spare parts supplied and accepted by Woods Air Movement. If any other spare parts are used,
then the warranty and EN-certification are no longer valid.
Spare parts:
• Fan motor
• Hatch motor
• Impeller
• Safety switches

13. PRODUCT CODE

Smoke extract fan
SMHA – AAA – BBB – CD – EF – PA
Fan Size
031, 040, 050, 080, 090,100, 125
Motor rating
048 = 4.8 kW.,etc.
C – Product Version
1 = Current version
D – Installation Accessories #1
E - Hatch casing colour / finish #2
F - High Temperature Category #3
PA – Fan pitch angle
NOTES:
Note #1 INSTALLATION ACCESSORIES (on fan inlet)
1 = Safety mesh (flat guard)
2 = Matching Flange
Note #2 HATCH CASING COLOUR / FINISH Options
1 = Galvanised
2 = Tele Grey 1 RAL 7045
3 = Window Grey RAL 7040
4 = Graphite Grey RAL 7024
5 = Jet Black RAL 9005
6 = White Aluminium RAL 9006
7 = Special Colour
Note #3 HIGH TEMPERATURE CATEGORY Options
3 = Ff300 (300°C/2 hours)
4 = F400 (400°C/2 hours)