Operating Instructions
for
Temperature Sensor
Model MWD
DT0621
page 1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MWD and is the answer not in the manual?

Questions and answers

Summary of Contents for Kobold MWD

  • Page 1 Operating Instructions Temperature Sensor Model MWD DT0621 page 1...
  • Page 2: Table Of Contents

    Disposal ............................ 12 Order codes ..........................12 EU-Declaration of conformity ......................13 UK Declaration of Conformity ....................... 14 Manufactured by: Kobold Mesura S.L.U Avda. Conflent 68 nave 15 08915 Badalona Tel.: +34 93 460 38 83 Fax: +34 93 460 38 76 E-Mail: info.es@kobold.com...
  • Page 3: Note

    Device model: MWD 4 Regulation Use The temperature sensors of the MWD Series are suitable for all applications where processes involving fluids, solid bodies or materials, or gases, require temperature recording and measurement. Our temperature sensors are suitable for use in the following industrial areas: chemicals, petrochemicals, water, feed, food, sanitary, etc.
  • Page 4: Operating Principle

    5 Operating Principle Resistance thermometers work by using the continuous change of resistance of metals subject to temperature rising and decreasing. The most common resistance material used is platinum, as it is very stable and has very good repeatability. The temperature coefficient of platinum is positive, so its resistance increases as the temperature rises.
  • Page 5: Sensor Wiring Diagram Without Head

    6.2 Sensor wiring diagram without head 2 wire 3 wire 4 wire DT0621 page 5...
  • Page 6: Transmitter Wiring Diagram

    6.3 Transmitter wiring diagram 6.4 Head model E wiring diagram page 6 DT0621...
  • Page 7: Head Model D Wiring Diagram

    6.5 Head model D wiring diagram 6.5.1 With transmitter 5333D 6.5.2 With transmitter 5337D 6.6 Head model R wiring diagram 6.6.1 With transmitter 5333D 6.6.2 With transmitter 5337D DT0621 page 7...
  • Page 8: Maintenance And Repairs

    7 Maintenance and repairs The instrument does not require maintenance or servicing. Repairs must be only carried out by Kobold (manufacturer) 8 Storage Measuring instruments should be protected against humidity and dust. Storage temperature: -40 ºC…+85 ºC for sensors without transmitter.
  • Page 9: Transmitter 5333D

    9.5 Transmitter 5333D Ambient temperature: -40...+85 ºC Power supply: 8...35 V Accuracy: Absolute accuracy ≤ ±0.3 ºC Temp. Coefficient (≤ ±0.01 ºC/ºC) Current Output: 4...20 mA Load resistance: ≤ (V supply - 8) / 0.023 Sensor error detection: Programmable 3.5…23 mA NAMUR NE43 Upscale and NAMUR NE43 Downscale 9.6 Transmitter 5337D...
  • Page 10: Display Type D/R

    9.9 Display type D/R Ambient temperature: -30...+80 ºC Loop voltage drop: Two levels depending on chosen backlight brightness at 20 mA: low bright backlight (<40%): max. 4 V at 23 ºC high bright backlight (>40%) max. 6.5 V at 23 ºC Accuracy: ≤...
  • Page 11: Trouble Shooting

    10 Trouble Shooting Faults Possible Causes Corrective actions No signal/line breakage Mechanical load too high or Replace probe or measuring over temperature. insert. Line breakage. Check wiring. Wrong measured values Sensor drift caused by over Replace probe or measuring temperature insert.
  • Page 12: Dismounting, Return And Disposal

    Residual media in dismounted instruments can result in a risk to persons, the environment and equipment. Take sufficient precautionary measures. All instruments delivered to KOBOLD must be free from any kind of hazardous substances (acids, bleaches, solutions, etc.). 11.2 Disposal...
  • Page 13: Eu-Declaration Of Conformity

    Normes harmonisées et documents normatifs appliqués Norme armonizzate e documenti normativi applicati: EN 61010-1:2011, EN 61000-6-2:2019, EN 60529:2018, IEC 61010-1:2016, IEC 61326-1:2021, IEC 60751:2022 Fabricado en KOBOLD MESURA SLU Avda. Conflent 68, nave 15 08915 BADALONA (Spain Made in: Hergesteltlt in: Fabriqué dans: Fabbricato in:...
  • Page 14: Declaration Of Conformity

    DICHIARAZIONE DI CONFORMITÀ UK KOBOLD MESURA SLU Avda. Conflent, 68 nave 15 08915 Badalona (España) We Kobold Mesura S.L.U. declare under our sole responsibility that the product: Temperature sensor MWD… To which this declaration relates is in conformity with the standards noted below: BS EN 61010-1:2010 Safety requirements for electrical equipment for measurement,controL, and laboratory use.
  • Page 15: Kobold Mesura S.l.u Avda. Conflent 68 Nave

    KOBOLD MESURA S.L.U Avda. Conflent 68 nave 15 08915 Badalona Tel.: +34 93 460 38 83 Fax: +34 93 460 38 76 E-Mail: info.es@kobold.com www.kobold.com Technical data Subject to change without prior notice DT0621 page 15...