Connect cables in accordance with the local installation laws and regulations.
To prevent poor cable connection due to overstress, leave enough slack before connecting the
cables to the appropriate ports.
4.1
Preparations
S and S
are the conductor cross-sectional areas of AC power cables and PE cables respectively.
p
The cable size must comply with local cable standards.
The factors that affect cable selection include the rated current, cable type, routing mode,
ambient temperature, and maximum expected line loss.
Cable Description
No. Cable
[1]
1
PE cable
Tracking system
2
power cable
AC output
power cable
(multi-core)
3
AC output
power cable
(single-core)
Type
Outdoor cable and M10 OT/DT
terminals
Three-core outdoor copper cable with
dual-layer protection
• If you connect a ground cable to the
ground point on the device enclosure
and the neutral wire is not used, you
are advised to use a three-core (L1,
L2, and L3) outdoor cable and M12
OT/DT terminals (L1, L2, and L3).
• If you connect a ground cable to the
ground point in the maintenance
compartment and the neutral wire is
not used, you are advised to use a
four-core (L1, L2, L3, and PE) outdoor
cable, M12 OT/DT terminals (L1, L2,
and L3), and M10 OT/DT terminals
(PE).
• If you connect a ground cable to the
ground point on the device enclosure
and the neutral wire is used, you are
advised to use a four-core (L1, L2, L3,
and N) outdoor cable and M12 OT/DT
terminals (L1, L2, L3, and N).
• If you connect a ground cable to the
ground point in the maintenance
compartment and the neutral wire is
used, you are advised to use a five-
core (L1, L2, L3, N, and PE) outdoor
cable, M12 OT/DT terminals (L1, L2,
L3, and N), and M10 OT/DT terminals
(PE).
You are advised to use a single-core
outdoor cable and M12 OT/DT
terminals.
Conductor Cross-
Sectional Area
S
≥ S/2
p
10 mm
• Copper cable
− S: 70–240 mm
− S
≥ S/2
p
• Aluminum alloy
cable or copper-
clad aluminum
cable:
− S: 95–240 mm
− S
≥ S/2
p
• Copper cable
− S: 70–240 mm
• Aluminum alloy
cable or copper-
clad aluminum
cable:
− S: 95–240 mm
5
Outer Diameter
2
15–18 mm
2
24–66 mm
2
2
14–32 mm
2