Out Of Service Mode - Kohler KD700 Operation

Industrial generator sets
Table of Contents

Advertisement

Operating
Action/Event
Mode
Press Auto or place the optional
keyswitch into the AUTO position (if
equipped).
Idle switch on contacts 5 and 6
closes.
Idle switch on contacts 5 and 6
AUTO
opens.
A warning condition occurs.
A fault condition occurs.
Press Manual or place the optional
keyswitch into the Manual position
(if equipped).
Press the Engine Start button or the
MANUAL
manual Start/Stop button (if
equipped).
Press the Engine Stop button or the
manual Start/Stop button (if
equipped).
Press the Out of Service button or
OUT OF
place the optional keyswitch into
SERVICE
the OFF position (if equipped).
Generator set shuts down on a
fault.
 The E-Stop button overrides the manual engine start/stop buttons and remote start signals. The engine will not start if the E-Stop button
is activated.
Figure 12
Operation Mode Summary
2.5.1

Out of Service Mode

Pressing the Out of Service button on the controller touchscreen disables the generator set to prevent starting during generator
set maintenance or service. The generator set remains off and will not respond to a remote start signal. If the generator set is
running, pressing the Out of Service button immediately shuts off the generator set, with no engine cooldown.
If a fault causes the generator set to shut down, the controller automatically enters the Out of Service mode.
Note:
To disable the generator set before servicing, shut down the generator set, place in Out-of-Service mode, and disconnect the
batteries negative (- ) lead first.
TP-7070
11/22
Operation
Responds to remote start/stop
commands from an ATS or remote start
panel. *
Engine runs at 1000 RPM for 5
minutes, then ramps up to normal
speed and voltage. *
Engine runs through the 5 minute
cooldown, then shuts down.
Fault button flashes orange.
Horn may sound, if connected.
Generator set shuts down and the fault
button flashes red. The mode changes
to Out of Service mode.
Horn may sound, if connected.
Engine can only be started and stopped
using the engine start/stop buttons on
the touchscreen or the manual
start/stop button (if equipped). *
Starts the engine if there are no active
faults. *
Stops the engine immediately, with no
engine cooldown.
Stops the engine immediately, with no
cooldown.
System is locked and generator startup
is not possible.
Notes
Auto is the recommended mode.
Customer-supplied idle switch is
required for idle mode operation.
Controller must be in Auto for idle mode
operation.
See the Events section for instructions
to view faults and warnings (alarms).
Engine start/stop is controlled manually
by the operator.
If equipped with the optional keyswitch
and manual Start/Stop button, the
engine start and stop buttons on the
controller touchscreen are disabled.
Use the manual Start/Stop button.
Wait 5 minutes after opening the circuit
breaker for engine cooldown before
pressing Engine Stop.
Put the generator set into Out of
Service (OFF) mode and disable the
generator set during maintenance or
service.
A fault shutdown automatically puts the
generator into Out of Service Mode.
See the Events section for instructions
to view and reset faults (shutdowns or
warnings).