2 Specifications
2.5A 120VAC 50/60 HZ, 1.25A 240VAC 50/60 Hz
AC power:
Power-limited (Class 2) 24V @ 1.5A each, Special Applications Aux Power, Aux 1 Class A/B, Aux 2 Class B only
24VDC aux outputs:
NAC outputs (power-limited):
lated, Class A/B Aux Power, UZC
carry CLP data and internal 24V power to the SLM-318 loop cards and the core board on the FACP CPU assembly. PMBs use
CLP Bus connections:
only the CLP data.
Secondary power (battery) charging circuit:
• Sealed lead-acid battery charger which will charge 7-100 AH batteries
• Charging current: 1A, 2A, and 4.25A
• Charging voltage: 27.6 VDC nominal
PMB battery charging configurations available (configured in VeriFire Tools):
• No charger
• Low (7-26AH)
• Medium (33-55AH)
• High (100AH)
3 Installation
The main FACP assembly should be mounted in the top row of the cabinet. Due to cable length restrictions, the PMB-AUX(-RTO) must be mounted in
the second position of the backbox. If installing two PMB-AUX(-RTO) power supplies, the second unit must be mounted in the third position. A max-
imum of two PMB-AUX(-RTO) units is allowed
Wiring methods used shall be in accordance with Standard for Installation and Classification of Burglar and Holdup Alarm Systems, UL 681.
WARNING: HIGH VOLTAGE PRESENT
!
REMOVE ALL SOURCES OF POWER BEFORE SERVICING, REMOVING, OR INSTALLING ANY UNITS. ENSURE TO
INSTALL THE SNAP-ON COVER OVER TB1 AFTER WIRING.
CAUTION: STATIC SENSITIVE EQUIPMENT
!
THE CIRCUIT BOARD CONTAINS STATIC-SENSITIVE COMPONENTS. ALWAYS USE PROPER GROUNDING DEVICES
SUCH AS A WRIST STRAP BEFORE HANDLING ANY BOARDS SO THAT STATIC CHARGES ARE REMOVED FROM THE
BODY. USE STATIC SUPPRESSIVE PACKAGING TO PROTECT ELECTRONIC ASSEMBLIES.
3.1 Requirements
Installations are to be indoors only, in dry locations, protected from rain, water, and rapid changes in temperature that could cause condensation.
Equipment must be securely mounted on rigid, permanent walls.
Operating temperature shall not exceed the range of 32° to 120° F (0 to 49° C).
Operating humidity not to exceed 93% +/- 2% non-condensing at 100° F (38° C).
Adequate space must be available around the installation to allow easy access for operation and servicing.
All sub-assemblies and components are to be located in compliance with local and national codes.
All installation field wiring shall be in compliance with local and national codes.
2
Special Applications Class A/B NAC Power, Class D Door Holder Power, 1.5A Special Applications, 150mA Regu-
PMB-AUX(-RTO) Power Supplies— P/N LS10242-000GE-E:B 5/4/2022