Honeywell NOTIFIER PAN1-PLUS Installation And User Manual page 3

Visual and acoustic fire alarm device

Advertisement

DIP 3OFF 4OFF
DIP 3ON 4OFF
S1
min dB(A) @1m min dB(A) @1m min dB(A) @1m
15
89
45
93
75
90
105
88
135
90
165
91
Installation:
Connection
Connect the main output with "polarity inversion" to positive (A+) and negative (A-) terminals (see. Pict.1)
with a certified wire. Moreover, insert the end-of-line R resistor between the "A+" terminal and the "A-"
terminal. The value of the end-of-line R resistor depends on the kind of main installed, and it is indicated in
the main installation manual.
Terminal SYNC (Synchronism): if required, connect together the terminal SYNC of the devices to
synchronize them.
Terminals B+ B- (Buzzer Mute): if required, applying 24Vcc between B+ and B- or short-circuiting B- with A-,
the buzzer is silenced.
OUTPUT WITH POLARITY
Selection of backlight mode
OFF - OFF (Default)
Selection of sound pattern and power
OFF - OFF (Default)
DIP 5OFF 6ON 94dB
DIP 3OFF 4ON
DIP 3ON 4ON
S2
S3
min dB(A) @1m
92
91
93
95
95
92
95
90
93
92
92
94
NEGATIVE IN STANDBY
CONNECT THE MAIN
INVERSION
POSITIVE IN STANDBY
DIP switch 1-2
ON – OFF
OFF - ON
ON – ON
DIP switch 3-4
ON - OFF
OFF - ON
ON - ON
DIP 3OFF 4OFF
S4
S1
min dB(A) @1m
90
15
85
94
45
93
90
75
98
88
105
93
90
135
100
93
165
89
Pict. 1
Description
Backlight blinking at 0.6 Hz
Backlight OFF
Backlight ON
Backlight OFF
Description
983Hz pulsed at 1.2 Hz
Sweep from 1200 Hz to 500 Hz at 1.2Hz
983-750 Hz alternate at 1.2Hz
983Hz continuous
DIP 5OFF 6ON 94dB
DIP 3ON 4OFF
DIP 3OFF 4ON
S2
S3
min dB(A) @1m
min dB(A) @1m min dB(A) @1m
94
85
93
95
97
99
95
95
97
101
93
91
R
SYNCRONISM
SYNCRONISM
MUTE BUZZER
DIP 3ON 4ON
S4
85
94
98
94
100
90