General features:
The panel PAN1-PLUS-EN3 is a device conceived for acoustic signaling of fires.
All materials utilized to produce it comply to fire system requirements and the housing is built with fireproof
materials.
The alarm device has to be installed by qualified personnel only, respecting all installation norms and
adequate distances and highness to get the best optical and acoustic performances.
Max Current absorption
Nominal Voltage supply
Max Power absorption
Max current absorption for sound
Main sound frequency (average)
Main sound pattern
Max level SPL @1 m
Available Patterns
Operating temperature
Command from the control panel
Enclosure protection degree
Size (WxHxD)
Weight
Standards
Installation and user Manual
Fire alarm devices - Acoustic alarm device
PAN1-PLUS-EN3
TECHNICAL DATA
S-312.1-PAN1P-EN3-ENG
PAN1-PLUS-EN3
Acoustic alarm device
50mA @Vdc=24V
24Vdc (from 20Vdc to 30Vdc)
1.2W
20mA +/-5mA
Sound 1 983 Hz
Sound 1 Pulsed at 1.2 Hz
See Diagram 1
4 available patterns: 1 modulated, 1 pulsed, 1 bitonal,1
continuous
From -10 °C to +55°C
Polarity inversion
IP21C (Type A, for indoor use)
307 x 117 x 55 mm
508 gr
EN54-3:2001 + A1:2002 + A2:2006
Rev. A.2 06/2019

Advertisement

loading

Summary of Contents for Honeywell NOTIFIER PAN1-PLUS-EN3

  • Page 1 S-312.1-PAN1P-EN3-ENG Rev. A.2 06/2019 PAN1-PLUS-EN3 Acoustic alarm device Installation and user Manual Fire alarm devices - Acoustic alarm device PAN1-PLUS-EN3 General features: The panel PAN1-PLUS-EN3 is a device conceived for acoustic signaling of fires. All materials utilized to produce it comply to fire system requirements and the housing is built with fireproof materials.
  • Page 2 Diagram 1 (Sound power distribution): LEFT Sound S2 – DIP - 5 OFF 6 OFF 97dBA 104dB RIGHT DOWN DIP 5OFF 6OFF 101dB DIP 5OFF 6OFF 101dB DIP 3ON 4ON DIP 3ON 4OFF DIP 3OFF 4ON DIP 3OFF 4OFF DIP 3ON 4ON DIP 3ON 4OFF DIP 3OFF 4ON DIP 3OFF 4OFF...
  • Page 3 Installation: Connection Connect the main output with “polarity inversion” to positive (A+) and negative (A-) terminals (see. Pict.1) with a certified wire. Moreover, insert the end-of-line R resistor between the “A+” terminal and the “A-” terminal. The value of the end-of-line R resistor depends on the kind of main installed, and it is indicated in the main installation manual.
  • Page 4 In case of any modification of one or more of the above topics, the certification will be not valid. 1293 Notifier s.r.l. Via A: Grandi, 22, 20097 S. Donato Milanese (MI) Italy DoP 1293 - CPR – 0602 EN54-3 PAN1-PLUS-EN3 FIRE ALARM DEVICES –...